&IGURE Pump curves for typical circulators suggested for DHW loop&IGURE Pipe sizing and head losses for DHW
applications
(H1=Ultra boiler head loss;
H2=piping head loss)
Flow
rate
Temp
rise
Pipe
size
H1 H2
GPM °F Inches
Boiler head
loss
Feet w.c.
Piping head
loss
Feet w.c.
5LTRA"TUHOUTPUT
7 20 1 6.6 2.7
9 16 1 11.6 4.2
10 14 1¼ 14.6 2.5
5LTRA"TUHOUTPUT
7 27 1 7.0 2.7
9 21 1 11.2 4.2
10 19 1¼ 13.6 2.5
13 14 1¼ 22.2 3.9
5LTRA"TUHOUTPUT
9 31 1¼ 6.2 2.1
10.0 28 1¼ 7.7 2.5
13 21 1¼ 13.3 3.9
16 17 1¼ 20.5 5.7
5LTRA"TUHOUTPUT
13 32 1¼ 9.4 3.9
16 26 1¼ 13.7 5.7
21 20 1½ 22.0 2.9
5LTRA"TUHOUTPUT
18 31 1½ 6.6 2.2
22 25 1½ 9.5 3.1
29 19 2 17.4 2.9
5LTRA"TUHOUTPUT
22 34 1½ 9.5 3.1
29 25 2 15.5 2.9
36 20 2 22.8 4.3
! "'0,
" Taco 0011
# Taco 0010
$ Taco 007
+ Taco 1400-30
% Taco 0013
& Grundfos 43-75
' Taco 0014
( Grundfos 15-42
* Taco 1400-20
, Taco 0012
®
SERIES 4 GAS-FIRED WATER BOILER — Boiler Manual
Sizing dire ct-connected DHW piping (continued)