User Guide

Part number 550-100-400/0717
36
Startup — fi ll the system (continued)
Freeze protection (when used)
Follow these guidelines to prevent pos-
sibility of severe personal injury, death
or substantial property damage:
.%6%2USEAUTOMOTIVEORSTANDARD
GLYCOLANTIFREEZE
,EVENGLYCOLMADE
FORHYDRONIC SYSTEMS
. Use only
freeze-prevention fl uids recommended
by Weil-McLain for application in Ultra
Boiler systems.
4HOROUGHLYmUSHANYSYSTEMTHAT
HASUSEDGLYCOL
before installing the
new Ultra boiler.
2EVIEW THE MATERIAL SAFETY DATA
SHEET-3$3
for the fl uid used with
the boiler owner and leave a copy for
reference. The MSDS contains informa-
tion on potential hazards and fi rst aid
procedures for exposure or ingestion.
#HECKANTIFREEZEINHIBITORLEVELAT
LEAST ANNUALLY
. Glycol concentration
and inhibitor levels may change over
time. Add antifreeze to increase con-
centration if necessary. Add inhibitor
as needed to bring to acceptable level,
using inhibitor test kit to verify.
When using freeze protection fl uid with
automatic fi ll,
INSTALLAWATERMETERTO
MONITORWATERMAKEUP
. Freeze pro-
tection fl uid may leak before the water
begins to leak, causing concentration
to drop, reducing the freeze protection
level.
$/ ./4 EXCEED  ANTIFREEZE
BYVOLUME
. Antifreeze moves more
sluggishly than water and can interfere
with heat transfer. At antifreeze concen-
trations higher than 50%, sludge can
develop in the boiler, potentially causing
damage to the heat exchanger.
#LEAN THE SYSTEM BEFORE FILLING.
Always drain and flush the system
thoroughly before fi lling with antifreeze.
Sludge, iron oxide deposits and other
sediment in the system inhibit fl ow and
can cause rapid breakdown of inhibi-
tors.
Use only antifreeze recommended by
Weil-McLain.
Weil-McLain provides information for
application of the antifreeze products
listed in this document only for use in
Weil-McLain Ultra boilers. Do not apply
these products or instructions for other
applications. Local codes may require a
backfl ow preventer or actual disconnec-
tion from city water supply.
Check/verify water chemistry
1. The system may have residual substances that could affect water
chemistry.
2. After the system has been fi lled and leak tested, verify water pH and
chlorine concentrations are acceptable.
3. Verify antifreeze concentration, when used.
4. Follow the instructions on the Sentinel test kit to sample the system
water and verify inhibitor concentration.
Check inhibitor concentration annually
1. Test the pH of a sample of system water at least annually. The pH of
the water mixture must be between 7.0 and 8.5. (Or use the Sentinel
inhibitor test kit to check concentration.)
2. If pH is outside this range (or inhibitor test kit indicates low level), the
inhibitor level may not be suffi cient to prevent corrosion.
3. Test antifreeze concentration.
Test antifreeze concentration at least annually. If concentra-
tion is low, add antifreeze or drain system and refi ll with
correct mixture.
4. Follow instructions on antifreeze container to determine the amount
of antifreeze needed.
$/./4 exceed 50% by volume concentration
of antifreeze.
5. Check inhibitor level after adjustments are made.
Purge air from water system
1. Connect a hose to the purge valve (see purge/drain valves, item 11, in
piping diagrams beginning on page 12 and page 52 . Route hose to an
area where water can drain and be seen.
2. Close the boiler or system isolation valve between the purge valve and
ll connection to the system.
3. Close zone isolation valves.
4. Open quick-fi ll valve on cold water make-up line.
5. Open purge valve.
6. One zone at a time, open the isolation valves. Allow water to run through
the zone, pushing out the air. Run until no noticeable air fl ow is present.
Close the zone isolation valves and proceed with the next zone. Follow
this procedure until all zones are purged.
7. Close the quick-fi ll water valve and purge valve and remove the hose.
Open all isolation valves. Watch that system pressure rises to correct
cold-fi ll pressure.
8. After the system has operated for a while, eliminate any residual air by
using the manual air vents located throughout the system.
9. If purge valves are not installed in system, open manual air vents in
system one at a time, beginning with lowest fl oor. Close vent when
water squirts out. Repeat with remaining vents.
10. Open automatic air vent (diaphragm-type or bladder-type expansion
tank systems only) one turn.
11. Starting on the lowest fl oor, open air vents one at a time until water
squirts out.
12. Repeat with remaining vents.
13. Refi ll to correct pressure.
®
SERIES 4 GAS-FIRED WATER BOILERBoiler Manual