User Guide

Part number 550-100-400/0717
34
U-Control operation and setup (continued)
EXPRESS SETUP — using default settings
1. The U-Control is factory programmed to supply a DHW circuit (control
priority 1) and fi nned tube baseboard space heating (control priority 2).
2. Control priority 3 is also available, and preset to run all three circulators
if desired, but requires settings to be confi gured.
&IGURE Factory default settings
0RIORITY 4YPE 4ARGETTEMPERATURE #IRCULATORS
ENABLED
1
DHW
Direct
190°F #1 Only
2
Finned
tube BB
180°F fi xed (if no outdoor sensor) or
180°F at 0°F outside / 130°F at 70°F
outside
#2 and #3
3 Custom
180°F fi xed (if no outdoor sensor) or
180°F at 0°F outside / 130°F at 70°F
outside
None
3. You can use the factory default settings for most systems supplying
space heating with fi nned-tube baseboard with or without a DHW
tank, provided:
a. A DHW tank, if used, must be piped directly to the boiler, as in the
piping shown in Figure 5, page 12 or Figure 6, page 13 .
b. If the DHW tank is a separate zone off of the system main, or if it is
piped as in Figure 48, page 52 , you will need to enable additional cir-
culators for DHW operation. The U-Control is factory programmed
to operate only the DHW circulator during DHW heating.
c. The heat emitters in the system must be fi nned tube baseboard
only. Other heat emitters require changes in the U-Control setup.
See ADVANCED INSTALLATION section for information.
4. Wiring to use the factory default settings — see information in
Figure 34, page 31 for wiring instructions.
&OR DETAILED CONTROL INFORMATION
AND ADDITIONAL WIRING
, see the
ADVANCED INSTALLATION
section of this manual.
,OWTEMPERATURE SYSTEMS (ra-
diant slab, etc.) — $/ ./4 use
the Ultra boiler control as the only
means of water temperature regula-
tion for low-temperature systems if
higher-temperature systems are also
supplied.
®
SERIES 4 GAS-FIRED WATER BOILERBoiler Manual