Install Instructions
Part number 550-100-090/1113
GAS-FIRED WATER BOILER — Boiler Manual
30
U-Control operation and setup (continued)
EXPRESS SETUP — using default settings
1. The U-Control is factory programmed to supply a DHW circuit
(control priority 1) and finned tube baseboard space heating (control
priority 2).
2. Control priority 3 is also available, and preset to run all three circulators
if desired, but requires settings to be configured.
&IGURE
Factory default settings
0RIORITY 4YPE 4ARGETTEMPERATURE #IRCULATORS
ENABLED
1
DHW
Direct
190°F #1 Only
2
Finned
tube BB
180°F fixed (if no outdoor sensor) or
180°F at 0°F outside / 130°F at 70°F
outside
#2 and #3
3 Custom
180°F fixed (if no outdoor sensor) or
180°F at 0°F outside / 130°F at 70°F
outside
None
3. You can use the factory default settings for most systems supplying
space heating with finned-tube baseboard with or without a DHW
tank, provided:
a. A DHW tank, if used, must be piped directly to the boiler, as in the
piping shown in Figure 5, page 12 or Figure 6, page 13.
b. If the DHW tank is a separate zone off of the system main, or if it is
piped as in Figure 48, page 48, you will need to enable additional cir-
culators for DHW operation. The U-Control is factory programmed
to operate only the DHW circulator during DHW heating.
c. The heat emitters in the system must be finned tube baseboard only.
Other heat emitters require changes in the U-Control setup. See
ADVANCED INSTALLATION section for information.
4. Wiring to use the factory default settings — see information in Fig-
ure 32, page 27 for wiring instructions.
&OR DETAILED CONTROL INFORMATION
ANDADDITIONALWIRING
, see the AD-
VANCED INSTALLATION section
of this manual.
,OWTEMPERATURE SYSTEMS (ra-
diant slab, etc.) —
$/ ./4 use
the Ultra boiler control as the only
means of water temperature regula-
tion for low-temperature systems if
higher-temperature systems are also
supplied.