User Guide

7
Part Number 550-142-301/0420
User’s Information Manual
Service technician
(covered in Boiler Manual – for use only by
a qualified service technician)
Owner maintenance
(see following pages for instructions)
AnnuAl stArt-up
Inspect:
•Reported problems
•Boiler area
•Air openings
•Flue gas vent system
•Pilot and main burner flames
•Water piping
•Boiler heating surfaces
•Burners, base and inlet air box
•Condensate drain system
Service:
•Oiled-bearing circulators
•Temperature/LWCO sensor
Start-up:
•Perform start-up per manual
Check/test:
•Gas piping
•Cold fill and operating pressures
•Air vents and air elimination
•Limit controls and cutoffs
•Expansion tank
•Boiler relief valve
Review:
•Review with owner
Daily
•Check boiler area
•Check air openings
•Check boiler pressure/
temperature gauge
Monthly
•Check boiler interior piping
•Check venting system
•Check air vents
•Check boiler relief valve
•Check automatic air vents
(if used)
Periodically
•Test low water cutoff
Every 6 months
•Operate relief valve
End of season
•Shut down procedure
Tankless water heater (EG and PEG only)
If boiler is used to supply domestic hot water, limit
control should be set to supply adequate hot water.
Weil-McLain tankless heaters are rated at 200 °F boiler
water temperature. To get rated output, set low limit at
200 °F. Limit can be adjusted to meet system hot water
requirements.Differentialcanbesetto15°andadjusted
to control level. Lowering the differential will cause a
slight variation in water temperature but will decrease
burner on-off cycling. High limit should be set at least
20 ° above low limit.
Maintain boiler using schedule below