Install Instructions
Part Number 550-142-902/1016
CGi
GAS-FIRED WATER BOILER — SERIES 3 — Boiler Manual
59
Troubleshooting — control module lights (cont.)
11c
CHART 7 –– Troubleshooting Sensor Ground and POWER light Solid
and/or “LCO” shown on display
Electrical shock hazard — Wherever you see ▲ TURN OFF POWER ▲, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
Is harness securely connected to control?
Yes No
• Control had poor connection,
boiler should resume operation.
• Secure connector.
Is the Sensor ground light still solid or flashing?
No Yes
• Check ground continuity from Pin 4 of P5
terminal to ground connection.
Is there continuity?
No Yes
• Secure wire to earth ground.
•
Retest.
Is the Sensor ground light still solid or
flashing?
No Yes
• Ground was improperly connected.
• Boiler should resume operation.
• Check for stray voltage on ground and
neutral wires.
Yes No
• Check and secure ground source to
earth ground connection.
Is the Sensor ground light still solid or
flashing?
Yes No
• Correct incoming power and ground-
ing issues.
• Replace control.