Check for gas leaks
Beforestartingtheboiler,anddur-
ing initial operation, smell near the
floor and around the boiler for gas
odorant or any unusual odor. Do
not proceed with start-up if there is
any indication of a gas leak. Repair
any leak at once.
Propane boilers only—Yourpro-
pane supplier mixes an odorant with
the propane to make its presence
detectable. In some instances, the
odorant can fade and the gas may
no longer have an odor.
• Propane gas can accumulateat
oor level. Smell nearthe oor
for the gas odorant or any un-
usual odor. If you suspect a leak,
do not attempt to light the pilot.
• Use caution when attempting
to light the propane pilot. This
should be done by a qualified
service technician, particularly
if pilot outages are common.
• Periodically check the odorant
level of your gas.
• Inspectboilerandsystematleast
yearly to make sure all gas piping
is leak-tight.
• Consultyourpropanesupplier
regarding installation of a gas
leak detector. There are some
products on the market intended
for this purpose.You r supplier
may be able to suggest an appro-
priate device.
Determine if water treatment is needed
Donot use petroleum-based cleaning or sealing
compounds
inboilersystem.Severedamagetoboiler
will occur, resulting in substantial property damage.
Eliminateall system leaks. Continualfresh makeup
waterwillreduceboilerlife.Mineralscanbuildupin
sections, reducing heat transfer, overheating cast iron,
and causing section failure.
Verify water chemistry
Consultlocalwatertreatmentcompaniesforunusuallyhardwaterareas
(above7grainshardness)orlowpHwaterconditions(below7.0).Boiler
waterpHof7.0to8.5isrecommended.
Freeze protection (when used)
Use antifreeze made especially for hydronic systems. Inhibited propylene
glycol is recommended.
Donotuseethylene glycol, automotive or undiluted
antifreeze
.Severepersonalinjuryordeathcanresult.
1. Determine
antifreeze quantity according to system water content.
Boilerwatercontentislistedonpage 70. Remember to include expan-
sion tank water content.
2. Follow antifreeze manufacturer’s instructions.
3. A50%solutionofpropyleneglycol/waterprovidesmaximumprotec-
tion to about -30°F.
4. Localcodesmayrequire
back ow preventer or actual disconnect from
city water supply.
5. When using antifreeze in a system with automatic fill, install a water
metertomonitorwatermakeup.Glycolwillleakbeforethewaterbe-
ginstoleak,causingglycolleveltodrop.Addedwaterwilldilutethe
antifreeze, reducing the freeze protection level.
Start-up — preparation
7a