Datasheet
Application
The digital Weigel Power Meters have been designed to display elec-
trical parameters in low voltage systems.
WPM 600 B - Z is suitable for use in 3 - phase 4 - wire systems 230/400 V.
This panel meter displays the following electrical parameters: voltage,
current, active power, reactive power, power factor, frequency, active
energy and reactive energy. The ratings are displayed one after the
other or can be selected by pressing a button.
Using the front - side buttons, the current transformer ratio can be set
and the energy values can be reset.
Functional Principle
Microprocessor-controlled digital measuring device that measures,
calculates and indicates electrical ratings.
WPM 600 B -Z has 3 voltage inputs and 3 current inputs to enable simul-
taneous evaluation of voltage, current and power for all three phases.
The meter must be connected via current transformers.
General Technical Data
Case
case details suitable to be mounted in switch gear panels
material of case plastics, black
panel fixing plastic clips
enclosure code IP 50 front of case
IP 20 rear of case
insulation voltage 2 kV
insulation resistance 50 MW
MTBF 50000 h
operating elements 4 membrane keys
Terminals 2 screw-terminal barrier strips
wire-cross section 2.5 mm
2
max.
Dimensions WPM 600 B - Z
bezel V 96 mm
bezel height 12 mm
panel cutout V 90
+0.5
mm
mounting depth 58 mm minus panel thickness
panel thickness
4 mm
weight approx. 0,5 kg
Electrical Data
system type 3 - phase 4 - wire system, unbalanced loads
rated voltage 230/400 V
rated current 5 A
current connection via CTs N/5 A
CT ratio adjustable 1 to 1999
overload capacity
current 1.2 times continously
10 times for 1 sec.
voltage 1.2 times continously
2 times for 1 sec.
frequency range 35 ... 65 Hz
Display
display 3x 4 - digit 7 - segment LED display, red,
and 8 red LEDs for measuring unit
digit height 15 mm
Measured Quantity LED WPM 600 B - Z Unit
voltage U 4 digits V
current I 4 digits A
active power P 4 digits kW
reactive power Q 4 digits kvar
power factor (cos ϕ) PF 3 digits –
frequency F 4 digits Hz
active energy E
P
9 digits *) kWh
reactive energy E
Q
9 digits*) kvarh
*) spread over 3 displays
Auxiliary Supply
auxiliary voltage 85 ... 265 V AC or 80 ... 300 V DC
power consumption <2 VA
Accuracy at Reference Conditions
voltage 0.5%
current 0.5%
power 1.0%
active energy class 1
Environmental
operating temperature –25 ... +70°C
range
storage temperature –40 ... +85°C
range
relative humidity 5% ... 95% non-condensing
Standards
DIN EN 61010–1 Safety requirements for electrical equipment
for measurement, control, and laboratory use –
Part 1: General requirements
DIN EN 61326–2–1 Electrical equipment for measurement, control
and laboratory use – EMC requirements –
Part 2–1: Particular requirements –
Test configurations, operational conditions
and performance criteria for sensitive test
and measurement equipment for
EMC unprotected applications