Datasheet
Data Sheet
800.D.101.07
Shunts
Class 0.5
Options (on Request)
rated voltage drop on request
rated current on request
accuracy class 0.2 produced in class 0.5
and calibrated to class 0.2 or
produced in class 0.2
(please order dimensional drawing)
insulating base suitable for shunts 30 ... 150 A / 60 mV
others on request
purpose built shunts on request
Accessory
cover for shunts with insulating base
1 ... 25 A / 60 mV – 100 mV – 150 mV
30 ... 150 A / 60 mV
Dimensions
format version A
with insulating base
with insulating base and cover
Attaching Disattaching
1
2
3
rated voltage drop 60 ... 300 mV 60 mV
dimensions (in mm) 1 ... 25 A 30 .... 150 A
a 90 100
b 78 80
c 20 20
d M5x12 M8x16
format version A without insulating base
rated voltage drop 100 mV 150 mV 300 mV
dimensions (in mm) 30 .... 150 A 30 .... 150 A 30 .... 150 A
a 145 225 384
b 125 205 364
c 25 25 25
d M8x16 M8x16 M8x16
format version B
e
a
b
c
d
f
g
10
rated voltage drop 60 mV
dimensions 200 A 400 A 1.000 A 1.500 A 2.500 A
(in mm) 250 A 600 A
a 145 145 165 165 165
b 105 105 115 115 115
c 30 40 60 90 120
d 30 30 30 30 30
e 15 20 30 21 30
f –– –4860
g M12x40 M16x45 M20x50 M16x45 M20x50
number of 2x 1 2x 1 2x 1 2x 2 2x 2
current connections
rated voltage drop 100 mV
a 190 190 210 210
b 150 150 160 160
c 30 40 60 120
d 30 30 30 30
e 15 20 30 30
f –– –60
g M12x40 M16x45 M20x50 M20x50
number of 2x 1 2x 1 2x 1 2x 2
current connections
rated voltage drop 150 mV
a 270 270 290
b 230 230 240
c 30 40 70
d 50 50 60
e 15 20 35
g M12x40 M16x45 M20x50
number of 2x 1 2x 1 2x 1
current connections