Datasheet

Application
Shunts provide an accurate DC millivolt signal to drive ammeter indica-
tors, overload protection and control devices, especially for higher am-
perage. They supply a voltage drop proportional to the DC current which
is measured and indicated by a moving–coil meter with the dial calibrated
in amps.
In accordance with DIN standard 43 703 shunts are available from 1 A up
to 15,000 A with an accuracy of 0.5%. Standard voltage drop is 60 mV or
150 mV. Intermediate current ratings, other voltage outputs, better accu-
racy and purpose–built shunts can be supplied.
Shunts are manufactured in three different format versions depending on
current ratings.
Operating Principle
The current passing through the shunt produces a proportional voltage
drop. A moving coil instrument connected to the shunt measures the
voltage drop across the shunt terminals.
Shunts are calibrated in such a way that they produce an accurately
defined voltage drop (60 mV, 150 mV or other).
General Data
format version A insulating base mounted shunts clamping
to DIN mounting rail or wall mounting
(up to 25 A / 60, 100, 150 or 300 mV);
without insulating base (30 ... 150 A) '
format version B L–profile end blocks
format version C T–profile end blocks
material
resistance bars manganin
end blocks
format version A high conductivity brass
format version B high conductivity brass/solid copper
format version C solid copper
base material Lexan, black
format version A self-extinguishing to UL rating 94 V–0
connections thread screws
current please refer to ”Dimensions”
voltage M5x8
mounting screw mounting (M8 max.) or
format version A clamping to DIN mounting rail
(to DIN EN 60 715)
enclosure code IP 00
dimensions please refer to ”Dimensions”
weight please refer to table below
rated current ' weight approx. for rated voltage drop '
60 mV 100 mV
1
) 150 mV 300 mV
1
)
1 A 0.10 kg 0.10 kg 0.10 kg 0.11 kg
1.5 A 0.10 kg 0.10 kg 0.10 kg 0.11 kg
2 A
1
)
2
) 0.10 kg 0.10 kg 0.10 kg 0.11 kg
2.5 A 0.10 kg 0.10 kg 0.11 kg 0.11 kg
3 A
1)
2
) 0.10 kg 0.10 kg 0.11 kg 0.11 kg
4 A 0.10 kg 0.10 kg 0.11 kg 0.11 kg
5 A
1)
2
) 0.10 kg 0.10 kg 0.11 kg 0.11 kg
6 A 0.10 kg 0.10 kg 0.11 kg 0.11 kg
8 A
1)
2
) 0.10 kg 0.10 kg 0.11 kg 0.11 kg
10 A 0.10 kg 0.11 kg 0.11 kg 0.11 kg
12 A
1)
2
) 0.11 kg 0.11 kg 0.11 kg 0.12 kg
15 A 0.11 kg 0.11 kg 0.11 kg 0.12 kg
20 A
1)
2
) 0.11 kg 0.11 kg 0.11 kg 0.12 kg
25 A 0.11 kg 0.11 kg 0.12 kg 0.13 kg
30 A
1)
2
) 0.12 kg 0.15 kg 0.16 kg 0.18 kg
40 A 0.12 kg 0.16 kg 0.17 kg 0.19 kg
50 A
1)
2
) 0.13 kg 0.16 kg 0.17 kg 0.20 kg
rated current ' weight approx. for rated voltage drop '
60 mV 100 mV
1
) 150 mV 300 mV
1
)
60 A 0.13 kg 0.16 kg 0.18 kg 0.22 kg
80 A
1)
2
) 0.13 kg 0.16 kg 0.19 kg 0.24 kg
100 A 0.13 kg 0.17 kg 0.21 kg 0.27 kg
150 A 0.13 kg 0.18 kg 0.24 kg 0.33 kg
200 A
1)
2
) 0.52 kg 0.55 kg 0.76 kg 0.88 kg
250 A 0.53 kg 0.58 kg 0.79 kg 0.94 kg
300 A
1)
2
) 0.79 kg 0.84 kg 1.12 kg 1.30 kg
400 A 0.79 kg 0.86 kg 1.18 kg 1.43 kg
500 A
1)
2
) 0.80 kg 0.88 kg 1.24 kg 1.55 kg
600 A 0.81 kg 0.90 kg 1.31 kg 1.68 kg
800 A
1)
3
) 0.82 kg 0.95 kg 1.42 kg 1.91 kg
1,000 A 1.44 kg 1.60 kg 2.52 kg 3.13 kg
1,200 A
1)
2
) 1.95 kg 3.00 kg 3.56 kg 4.30 kg
1,500 A 1.98 kg 3.08 kg 3.76 kg 4.68 kg
2,000 A
1)
2.01 kg
3
) 3.19 kg
3
) 5.20 kg
2
) 6.42 kg
2
)
2,500 A 2.91 kg 4.55 kg 5.52 kg 7.06 kg
3,000 A
1)
2.94 kg
3
) 4.66 kg
3
) 9.87 kg
2
) 11.70 kg
2
)
4,000 A 4.26 kg 8.93 kg 10.00 kg 12.98 kg
5,000 A
1)
4.33 kg
3
) 9.19 kg
3
) 13.60 kg
2
) 16.68 kg
2
)
6,000 A 10.93 kg 11.89 kg 14.22 kg 17.92 kg
8,000 A
1)
11.08 kg
3
) 25.30 kg
2
)–
10,000 A 21.05 kg 26.54 kg
15,000 A 31.7 kg
20,000 A
1)
37.2 kg
1
) ratings deviating from DIN standard
2
) dimensions equal to next higher current rating
3
) dimensions equal to next lower current rating
overload range
continuously 1.2 times rated current
5 s max.
2,000 A 5 times rated current
>2,000 ... 10,000 A 2 times rated current
Accuracy at Reference Conditions
accuracy class 0.5 '
reference conditions
ambient temperature 23°C±1K
Environmental
climatic suitability climatic class 3 acc. to VDE/VDI 3540
operating –10 ... +55°C
temperature range
storage –25 ... +65°C
temperature range
relative humidity
75% annual average, non–condensing
Rules and Standards
DIN 43 703 Shunts
DIN EN 60 051 Direct acting indicating analogue electrical
measuring instruments and their accessories
–1 Part 1: Definitions and general requirements
common to all parts
–8 Part 8: Special requirements for accessories
–9 Part 9: Recommended test methods
DIN EN 60 715 Dimensions of low voltage switching devices:
standardized DIN rails for mechanical fixation
of electrical devices in switchgears
' for other ratings refer to ”Options”