User manual

Weidmuller Wireless Ethernet Modem & Device Server WI-MOD-E-G/A User Manual
Rev.2.16 www.weidmuller.com 88
4.9 - Internal diagnostics Modbus Registers
There are a number of internal diagnostic registers that can be accessed via Modbus TCP/RTU that will help with
analyzing and diagnosing the radio network. To access these register the Modbus Server will need to be enabled and a
Modbus Server address will need to be configured (See 3.15 - “Modbus I/O Transfer” for details on how this is done).
After enabling the Modbus Client you can then access the following information by reading the corresponding Modbus
Address at the Server ID address.
Note: ‘wi0’ is the normal default interface. If more interfaces are added by entering in virtual WDS
connections (either Client or AP) in section 3.17 - ”Repeaters (WDS)” then they will take on the next
available interface number i.e. wi1, wi2, etc
Connection Information
Register Module Description
5000
Both Total number Associated Stations
5001
Both Current Radio Channel. See section 3.9 - “Radio Configuration” for
channel details
5002
Both Number Wireless Interfaces configured, includes Virtual Interfaces –
wi1-wi10
5010
Both Wireless Adaptor (wi0) - Link Status
5011
Both Wireless Adaptor (wi0) - Link Status Inverted
5012
Both Wireless Adaptor (wi0) - Number Associated Stations for this
interface
5013
AP Only
Wireless Adaptor (wi0) - Points to the starting register of the AP's Station
List. First interface (wi0) will always start at 5200 and dynamically enter data
depending on the number of STA’s. Remaining interfaces (wi1-wi10) will be
entered after wi0 data. Register 5023, 5033, etc will indicate starting location
for each interface.
5014
STA Only
Wireless Adaptor (wi0) – RSSI & BGND of Rx message from AP e.g. Hex
5F5D = 5D for RSSI and 5F for BGND (Convert value from hex to dec and
add a “-“ e.g. 5F = -95dB)
5015
STA Only Wireless Adaptor (wi0) - Transmit Data Rate from the Access Point
5016
STA Only Wireless Adaptor (wi0) - MAC Address of the Access Point
5020-5026
As per 5010-
5016
As per registers 5010-5016 but for the next Wireless Adaptor (wi1)
5030-5036
As per 5010-
5016
As per registers 5010-5016 but for the next Wireless Adaptor (wi2)
5040-5046
As per 5010-
5016
As per registers 5010-5016 but for the next Wireless Adaptor (wi3)
……etc
As per 5010-
5016
As per registers 5010-5016 but for the next Wireless Adaptor (wi10)
5200
AP Only RSSI of the Client (STA)
5201
AP Only Transmit Data Rate to Client (STA)
5202
AP Only MAC address of Client (STA)
…..etc
AP Only Dynamic list of STA's Refer to register 5023, 5033, etc for starting
register of each wi interface
9999
Both Reset module (enter FFFF to reset module)