Chapter 5 SPECIFICATIONS
General
WI-I/O 9-x Radio standards FCC Part 15A, Part 15.247 902 – 928 MHz, 1W
WI-I/O-1-x Radio standards
FCC Part 90, Part 15, RSS-
119
380 – 520 MHz, 12.5 / 25KHz, 0.5 –
5W
Housing 130 x 185 x 60mm
DIN rail mount
Refer section 5.1 for
dimensioned drawing
Powder-coated, extruded aluminium
Terminal blocks Removable Suitable for 12 gauge / 2.5 mm
2
conductors
LED indication Power supply/OK, Active
operation, digital I/O,
Radio RX and TX, Serial
RX and TX
Operating Temperature WI-GTWY-9-MD1
WI-GTWY-9-PR1
WI-GTWY-9-ET1
WI-GTWY-9-DE1
WI-GTWY-9-M+1
-40 to 140 degF, -40 to 60 degC
30 to 140 degF, 0 to 60 degC
30 to 140 degF, 0 to 60 degC
30 to 140 degF, 0 to 60 degC
30 to 140 degF, 0 to 60 degC
Humidity 0 – 99% RH
non-condensing
Power Supply
Battery supply 11.3 - 15.0 VDC
AC supply 12 - 24 VAC, 50/60 Hz
Overvoltage protected
Battery required for 105U units with
more than 2W RF power
DC supply 9 - 30 VDC Overvoltage and reverse voltage
protected
> 17VDC required for charging battery
Battery required for 105U units with
more than 2W RF power
Battery Charging circuit Included, suitable for
12Vsealed lead acid
batteries
Regulated to max 1.5 amp charging
current
Normal Current Drain at
12VDC
WI-GTWY-9-xxx-MD1
WI-GTWY-9-xxx-other
150 mA
270 mA
270 mA
add 5mA per active I/O