User manual

WI-GTWY-9-xxx Wireless Gateway V1.18
124
amount of time, the WI-GTWY-9-xxx will timeout and disconnect that connection. Note that
there can be several active connections at the same time - only the inactive connection will be
disconnected.
Enable Ethernet Debug
Select this box if you wish to enable Ethernet Diagnostics on the WI-GTWY-9-xxx via
configuration software (see section 6.3 for details). For security reasons, disabling this option
will disallow all Ethernet diagnostics functions accessible to configuration software, and can only
be reactivated via serial port configuration.
4.12.2 Modbus TCP
To use Modbus TCP, select the Enable Modbus Server box and deselect the Enable Ethernet/IP
box. This will automatically remove the “I/O Instance” selection for all fieldbus mappings. It is
possible for both Modbus TCP and Ethernet/IP to be selected - in this case, select “Disable I/O
Instance” individually for each Modbus TCP fieldbus mapping.
Supported Commands:
Function
Code
Function Name Class Affects Area Address Method
1 Read coils 1 IN/OUT Bit
2 Read Input discretes 1 IN/OUT Bit
3 Read multiple registers 0 IN/OUT Word
4 Read input registers 1 IN/OUT Word
5 Write coil 1 OUT Bit
6 Write single register 1 OUT Word
7 Read exception status 1 - -
15 Force multiple coils 2 OUT Bit
16 Force multiple registers 0 OUT Word
22 Mask write register 2 OUT Word
23 Read/Write registers 2 IN/OUT Word
Supported Exception Codes:
Exception
Code
Name Description
01 Illegal function The module does not support the function code in the query
02 Illegal data address The data address received in the query is outside the
initialized memory area
03 Illegal data value The data in the request is illegal