Installation guide

26 PV Clinics Installation Manual 21/07/11 01.00 01/12
6.6 Register Values
6.6.1 Holding Register Values
REGISTER 40002:
MAXIMUM CURRENT OF EACH STRING
Register VALUE
For MODULE Type:
01 02 03 04 05 06 07 08 09 10 11 12 13 14
1
CPU + 4xi
30A
30A
30A
30A
-
-
-
-
-
-
-
-
-
-
-
-
2
CPU + 8xi
30A
30A
30A
30A
30A
30A
30A
30A
-
-
-
-
-
-
-
-
4
CPU + 7xi
20A
20A
20A
20A
20A
20A
20A
-
-
-
-
-
-
-
-
-
5
CPU + 14xi
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
REGISTER 40003 to 40016: Current OFFSET Correction of every STRING (STR1 to STR14).
REGISTER 40020 to 40036: Current GAIN Correction of every STRING (STR1 to STR14).
REGISTER 40017: Voltage OFFSET Correction of V1.
REGISTER 40034: Voltage GAIN Correction of V1.
REGISTER 40019: Temperature OFFSET Correction of T1.
REGISTER 40036: Temperature GAIN Correction of T1.
REGISTER 40037: Digital Output Command: 0--> turn off, 1--> turn on
REGISTER 40038 and 40041: Value OFFSET Correction of every Analog input (Analog1 and Analog2).
REGISTER 40039 and 40042: Value GAIN Correction of every Analog input (Analog1 and Analog2).
6.6.2 Input Register Values
The input registers contain instantaneous and RMS values of string Currents, Voltage, Module Temperature
and the analogue input values; Hardware and Software revisions; and the digital input status.
REGISTER 30001: Digital Inputs Status: IN1 and IN2
REGISTER 30002 to 30015: Instantaneous Current of every STRING (STR1 to STR14).
REGISTER 30019 to 30032: RMS Current of every STRING (STR1 to STR14).
REGISTER 30016: Instantaneous Voltage of V1.
REGISTER 30033: RMS Voltage of V1.
REGISTER 30018: Instantaneous Temperature of T1.
REGISTER 30035: RMS Temperature of T1.
REGISTER 30038 and 30040: Instantaneous Value of Analog Inputs (Analog1 and Analog2).
%of the MAXIMUM Value (20mAor10V)
REGISTER 30039 and 30041: RMS Value of Analog Inputs (Analog1 and Analog2).
%of the MAXIMUM Value (20mAor10V)
REGISTER 30036: HARDWARE Version “Version:
REGISTER 30037: SOFTWARE Version 00.01 to 99.99”