IE-GPRS-I/O Alarm Modem Weidmüller Interface GmbH & Co. KG Klingenbergstraße 16 32758 Detmold Tel.: 0 52 31 / 14-0 Fax: 0 52 31 / 14 20 83 V 2.
Copyright Weidmüller Interface GmbH & Co. KG. All rights reserved. All rights are reserved, including those of translation, reprinting, and reproduction of this manual, or parts thereof. No part of this manual may be reproduced, processed, copied, or transmitted in any way whatsoever (photocopy, microfilm, or other method) without the express written permission of Weidmüller Interface GmbH & Co. KG, not even for use as training material, or in using electronic systems.
Contents 1 Safety Notes 1-4 1.1 Graduated safety notes 1-4 1.2 Definitions 1-4 1.3 Hazards resulting from use other than as described 1-5 1.4 Hazards resulting from modifications and upgrades 1-5 1.5 1.5.1 1.5.2 1.5.3 Admitted personnel Operator Start-up engineer Service engineer 1-5 1-6 1-6 1-6 1.6 Electrical connections 1-7 1.7 Safety regulations 1-7 1.8 Service and maintenance 1-8 1.9 Waste disposal 1-8 1.10 Liability 1-9 2 Use as Prescribed 2-10 2.
Contents 3-24 3-25 3-25 3.4.2 3.4.3 3.4.4 Remote servicing The "Passive" mode The "Transparent" mode 4 Configuring the IE-GPRS-IO 4.1 4.1.1 4.1.2 Configuring the via the RS 232 interface 4-26 Setting up the virtual modem and the long-distance data transmission connection under Windows XP/2000 4-26 Installing the long-distance data transmission connection 4-29 4.2 4.2.1 Making the settings General Settings 4-38 4-40 4.3 4.3.1 Access to the device Device Access 4-42 4-42 4.
Contents 5.4 Storage and storage temperatures 5-75 5.5 Operating temperature, humidity 5-75 5.6 5.6.1 5.6.2 5.6.3 5.6.4 Status display Display "POWER on/off" "Status" display "Line" display "Ports" display 5-76 5-77 5-77 5-77 5-78 5.7 5.7.1 5.7.2 5.7.3 Connections / interfaces Power supply RS232 Inserting the SIM card 5-79 5-79 5-80 5-80 6 Technical Data 6-84 7 Standards and Certifications 7-86 7.1 Harmonised standards 7-86 7.2 Certification to DIN EN ISO 9001 7-86 7.
Safety Notes 1 Safety Notes 1.1 Graduated safety notes In this Instruction Manual, safety notes are marked with a symbol and the keyword CAUTION or NOTE at the page margin. Safety notes are printed in bold letters and are marked with an outside border. 1.2 Definitions The keyword DANGER is used to warn you of a possibly hazardous situation. DANGER DANGER of electric shock is used to warn of a possibly hazardous situation involving electric current.
Safety Notes 1.3 DANGER Hazards resulting from use other than as described Use other than as prescribed may result in personal injuries to the user or third persons, as well as in material damage to the control system or the product, or in environmental damage. The IE-GPRS-I/O must only be used according to its intended purpose! 1.4 Hazards resulting from modifications and upgrades Unauthorised modifications and amendments are not permitted.
Safety Notes 1.5.1 Operator The operator: • is an instructed person • who is authorised to turn on / turn off the equipment 1.5.2 Start-up engineer The start-up engineer: • is an electrical expert • must be an expert in parameterising the device • who carries out the start-up, observing strict precautions and • carries out the required test 1.5.
Safety Notes 1.6 Electrical connections The IE-GPRS-I/O must be connected to an electrical supply system. Power supply connection The IE-GPRS-I/O must only be connected to the electrical supply system by an electrical expert. DANGER The power supply of the IE-GPRS-I/O must be provided exclusively by a power pack which complies with DIN EN 60 742 (VDE 0551). Make sure that an appropriate fuse is installed in the incoming supply feeder.
Safety Notes 1.8 Service and maintenance Service and maintenance work Improper service and maintenance may result in loss of life, personal injuries, material damage or environmental impairments. DANGER Service and maintenance work, as well as troubleshooting, must only be carried out by qualified expert personnel.
Safety Notes 1.10 Liability The contents of the present Instruction Manual are subject to technical modifications, which may result, in particular, from the continuous further development of the products made by Weidmüller. Weidmüller will not assume any liability for printing errors or any other inaccuracies contained in the present Instruction Manual, unless these are serious errors which are evidently known to Weidmüller.
Use as Prescribed 2 Use as Prescribed 2.1 Range of application The Alarm Modem IE-GPRS-I/O is designed to collect messages in industrial plants and building installations. The messages are detected as activated switching contacts and analog limit values. Via a serial protocol, the higher-level plant or system may either receive data or control the data traffic itself.
Use as Prescribed Do not use the IE-GPRS-I/O in potentially explosive areas! Danger When connecting the device, observe, in particular, the information provided in the following sections: • 1.6 Electrical connections • 5 Hardware • 6 Technical Data.
Description of Functions 3 Description of Functions 3.1 General Description of Functions The IE-GPRS-I/O provides comprehensive configuration possibilities for messaging services. The IE-GPRS-I/O can be online permanently. It checks and maintains the connection once established. No costs arise, except the fixed monthly charge. Depending on the M2M tariff, a certain data volume for sending messages is also included.
Description of Functions • 3.2 Low purchasing costs and cost-effective operation thanks to special M2M-GPRS tariffs. Functions of the interfaces 3.2.1 Digital inputs Binary inputs for detection of external states as a high or low signal • Electrically isolated and floating in two groups: • Number: 8 • Input voltage: 0 … 30 VDC • Input voltage status 0: 0 … 4 V / 0 … 1.2 mA • Input voltage status 1: 10 … 30 V / 1.5 … 4.
Description of Functions 3.2.2 Analog inputs Analog inputs for detection of external states as violation of minimum or maximum limit values or as a percentage deviation; can be used to measure voltage, temperature or current.
Description of Functions 3.2.3 Digital outputs The binary outputs can be used as follows: • Signalling of successful/failed messages, see Section 4.6 Alarm Message and 4.9 Function control. • Remote-switching via telephone using tone dialling, see below • Switching from another IE-GPRS-I/O of a group via X-Rec, see Section 4.4 Digital inputs and outputs (Digital I/O) Digital outputs • Operating voltage: Output current: 10 … 30 VDC max.
Description of Functions 3.2.4 Serial interface The serial interface serves for communication with the monitored plant or for communication of the plant with the connected devices via the IE-GPRS-I/O. The parameterisation and any firmware updating for the IE-GPRS-I/O are performed via the serial interface. The communication via the serial interface requires a fully connected 1 : 1 cable. Regarding the information required to configure the serial interface, please refer to Section 4.11 COM. NOTE 3.2.
Description of Functions 3.2.6 GSM modem The GPRS module realises a virtual dedicated line. With an M2M GPRS tariff of a mobile telephone provider, the only costs in addition to a low fixed monthly charge are the costs for the actual data transfer. No permanently installed fixed-network telephone connection is required. Each IE-GPRS-I/O can be accessed online at any time in the same way as a mobile telephone.
Description of Functions 3.3 Settings of the operating system 3.3.1 (Firmware) update for the operating system The operating system of the IE-GPRS-I/O is subject to continuous further development to adapt it to the technical requirements and customer wishes. Devices which are already in use may thus also require a new operating system. The version of operating system currently installed on your IE-GPRS-I/O can be displayed on the About page of your web browser (see Section 4.
Description of Functions • The loading process will take approx. 5 min. • Once loading is completed successfully, OK is displayed in the status line. If the Loader does not permit any choice in the COM window, the interfaces may already be occupied either by a driver of installed software or by an application which is currently running. NOTE The version number can also be displayed via the serial interface using a terminal program.
Description of Functions 3.3.2 Resetting to the factory defaults If you wish to reset the IE-GPRS-I/O to a defined initial state, you can load the factory settings: • Turn off the IE-GPRS-I/O. • Set the DIP switch to 1-1-0-0. • Turn on the IE-GPRS-I/O. • The LEDs 1 … 4 will flash yellow for 5 s. • The LEDs 1 … 4 will go out one after the other. • The status LED flashes red. • The factory settings are now loaded. • Turn off the IE-GPRS-I/O. • Set the DIP switch to 1-0-0-0.
Description of Functions 3.4 NOTE Communication between PC and IE-GPRS-I/O The communication is realised via a serial connection. To display the HTML user interface of the IE-GPRS-I/O, Microsoft Internet Explorer, version 5.5 or higher is required. For the relevant information required to configure the IE-GPRS-I/O via the serial interface, please refer to Section 4.1. To configure the IE-GPRS-I/O using the HTML user interface, it is imperative to know the current Ethernet address of your IE-GPRS-I/O.
Description of Functions 3.4.1 Diagnosis using a terminal program ATTENTION If Windows HyperTerminal is used, previous activities, which may also have arisen from other communication instances, are displayed outside the visible window but can be viewed in the fullscreen mode. You should therefore set the view in the Terminal window in the View menu to Fit to Window Size. • Set and configure the serial interface to be used for the terminal program: • Disconnect the operating voltage.
Description of Functions Diagnosis is also possible in the messaging mode. Messages: Reset Hardware The IE-GPRS-I/O has been restarted. Mon, 16 Jan … Date, time and time zone of the IE-GPRS-I/O DI1 … 8 S 1s Normally open contact Debouncing set; the signal must have been V Analog input set to voltage measurement 1s Debouncing set; the signal must have exceeded or fallen below the level for 1 s. present for 1 s.
Description of Functions 3.4.2 Remote servicing It is possible to make all settings for the IE-GPRS-I/O from a remote PC. To do so, you will need an analog modem. The connection to the IE-GPRS-I/O is again established via "Dial-Up Networking". In "Properties" of "Dial-Up Networking", set the analog modem as the transfer device. Enter the number of your IE-GPRS-I/O as the dialling number; the dialling number is indicated in your SIM-card agreement.
Description of Functions 3.4.3 The "Passive" mode The "Passive" mode provides a data connection from a remote PC, via a modem and the IE-GPRS-I/O to a device connected to the serial interface of your IE-GPRS-I/O. Procedure • The PC calls the IE-GPRS-I/O via a modem. • The IE-GPRS-I/O accepts the call and establishes a connection.
Configuration 4 Configuring the IE-GPRS-IO To start up your IE-GPRS-I/O, it must be configured first. The individual steps for starting up will be explained in the present chapter. 4.1 Configuring the IE-GPRS-I/O via the RS 232 interface The IE-GPRS-I/O is connected to a PC via the RS 232 interface "RS232" using a modem cable. The RS232 protocol is used directly. The IE-GPRS-I/O is addressed using Internet Explorer 5.5 or higher.
Configuration • The wizard assisting you in setting up a new modem is started: • ; Select Don't detect my modem. select: I will select it from a list. • • Select your modem from the following window: (default modem type) -> default modem 33,600bps • Select the interface on your PC to which your IE-GPRS-I/O is connected: COM1 or COM2 If an interface on your PC is not displayed, but is known to exist, it is probably currently occupied by another interface driver, e.g. a CAPI driver.
Configuration • Select Start – Settings – Control Panel - Phone and Modem Options and there select • the new modem: • - "General" tab • Make sure that Use this device (enable) is selected: • "Modem" tab: Select 38400 as the maximum transfer rate. • "Diagnostics" tab: Nothing need be entered here. • "Advanced" tab: Nothing need be entered here. • "Driver" tab: Do not make any changes here.
Configuration 4.1.2 Installing the long-distance data transmission connection • Select Start - Settings – Control Panel – New Connection Wizard; • The wizard assisting you in establishing a new connection is started.
Configuration • • Assign the long-distance data transmission connection a name: • Enter any number: • ; Add a shortcut to this connection on my desktop • 4-30
Configuration After setting up is completed, the connection to the IE-GPRS-I/O can be called directly by clicking on the shortcut on the desktop. To do so, the Internet Explorer need not be reconfigured. NOTE If no shortcut was created on the desktop, the connection can also be called directly under Start – Settings – Network Connections - IE-GPRS-I/O . "IE-GPRS-I/O" stands for the name selected for the connection.
Configuration • "General" tab: Make sure that only the previously installed modem is selected.
Configuration • "Dialling Rules" tab: • ~ My Location - The once selected location is displayed. • • "Options" tab: • ; Display progress while connecting • ; Prompt for name and password, certificate, etc.
Configuration • "Security" tab: • ~ Security options Typical Allow unsecured password • No further checkboxes must be set.
Configuration • • ; Enable LCP extensions •
Enable software compression must not be selected.
Configuration • ; Use default gateway on remote network • PPP link:
Use IP header compression must not be selected.
Configuration • ~ Disable NetBIOS over TCP/IP must be set. • … Back to "Properties of IE-GPRS-I/O" • Advanced – Settings tab • | "On" must not be set! • … - until all windows are closed.
Configuration 4.2 Making the settings The configuring tool required is Internet Explorer 5.5 or higher. Starting configuring • Disconnect the operating voltage. • Set the DIP switch Options on the IE-GPRS-I/O for the configuring mode to 1-0-0-0 (ON-OFF-OFF-OFF). • Connect the serial interconnecting cable (1 : 1). • Reconnect the operating voltage and wait until the Power LED lights green and the Status LED flashes red.
Configuration Once the page is open, you can save the address of your IE-GPRS-I/O as a favourite (bookmark) in the Internet Explorer. ATTENTION The appearance and contents of the windows depend on the firmware version installed. The appearance may deviate from the illustration shown here. Furthermore, the screen display is influenced by the browser and its settings. No language selection is possible in the present version.
Configuration 4.2.1 General Settings The general settings apply for the device as a whole. Station number • Dialling number used to call the station; is supplied with your SIM card when the contract is concluded with the mobile telephone provider. • A number must always be entered. • If you are uncertain, "1" can be left for the time being, and you can change the number later (also remotely). • This number is transmitted where appropriate, e.g. in the fax identification. • Max.
Configuration Quit Pin • 4-digit sequence of digits which is used to acknowledge SMS and voice messages. Acknowledgement must be enabled in the menu Messages with a þ , i.e. acknowledgement of the messages is imperative (see Section 4.6). • Only digits may be used. • If 0000 is entered, you can use any numeric key of your telephone; in this case, only one key must be pressed. • Always 4 digits.
Configuration Text Header • Here you can enter a text that can be inserted in the message texts using the text block #HEAD#. • For example, the name of the plant or the name of the company can be entered, or a description of the states of the digital I/Os. • Max. 80 characters. • For further fixed text blocks, see Section 4.6 Safety Notes. 4.3 Access to the device 4.3.1 Device Access These settings control the access to the device.
Configuration User name for PPP • User name used to connect via "Dial-Up Networking, whether remotely or locally; see "Configuring the long-distance data transmission connection", Section 4.1.1. • Max. 30 characters Password for PPP choice • User name used to connect via "Dial-Up Networking", whether remotely or locally, if the device is to be accessed via voice. • Max.
Configuration Certified dialling numbers ATTENTION • Dialling numbers of fixed/mobile telephones and modems from which a remote access is to be granted to the device. • 8 access numbers are possible. • If no numbers are entered, access is possible from any dialling number. • The dialling number must have the format +49123456789; no blanks or special characters are allowed. If one or several numbers are entered here, access to the device can only be realised from one of these numbers.
Configuration 4.4 Digital inputs and outputs (Digital I/O) Active on • High: A message can be triggered if a voltage in the range 12 ... 24 V is present at the input. • Low: A message can be triggered if a voltage of 0 V is present at the input. • Level change: A message can be triggered if the input voltage changes from 0 V to 12 ... 24 V or vice versa. The input voltage must NOT lie within the range of 4 … 10 V. In this voltage range, no reliable status detection is provided.
Configuration Debouncing time • The relevant input signal must have been present without interruption for at least the set debouncing time for a message to be triggered; shorter disturbances cannot trigger a message. Text for High • A text that can be inserted into the message block using the text block #VAL# or #DI1#...; thus, it is possible to modify the message text dynamically, depending on the particular event. • Max. 16 characters.
Configuration The switching time is not effective when switching the digital outputs remotely via telephone. ATTENTION X-Rec ATTENTION • Remote-switching by a digital input of another IE-GPRS-I/O in a group of IE-GPRS-I/Os • Two IE-GPRS-I/Os are included in a group. ; Connects the IE-GPRS-I/O as the receiving device of the group to the digital input of the sending IE-GPRS-I/O.
Configuration Measured unit • Selection of the analog measurement unit: Volt Ampere Temperature Measured value • This field displays the measured value of the inputs. • Clicking on the field refreshes the measured values of the two analog inputs. Factor • It is possible to scale the measured value with a factor. In this case, the calculation is performed as follows: (Factor ∗ measured value) + offset, i.e.
Configuration • dynamically, depending on the particular event; max. 16 characters. Report • If this field is checked, a message is triggered when the upper limit value is exceeded. Lower limit value • If the measured value is lower than the lower limit value, a message can be triggered. • Further messages can only be triggered if the measured value has risen above the upper limit value and has then again fallen below the lower limit value.
Configuration 4.6 Alarm Message Input • The following events can be selected to trigger a message: REPORT An error has occurred, e.g. faulty login into the GPRS network DI1 ... DI4 Digital inputs 1 to 8 AI1 … AI2 Analog inputs 1 and 4 EI1 … EI16 Signal inputs, serial, via the TUP protocol Text • Enter the text you wish to be displayed in the message in the text field, for example "Fault: Pump". • The maximum length permitted, including all text blocks, is 160 characters.
Configuration ▫ #VAL# Inserts the text for the input belonging to the message, depending on its value at the time when the message was triggered. ▫ #DI1# ... DI8# Inserts the text for the digital input belonging to the message, depending on its value at the time when the message was triggered. ▫ #AI1# ... AI4# Inserts the measured value and its unit for the analog input, depending on its value at the time when the message was triggered.
Configuration ▫ The message targets form a message sequence. The message sequence is interrupted if a target of this sequence was informed successfully, including acknowledgement. ▫ If a message target is to be informed in any case, irrespective of its position in the message sequence, the message targets must be marked additionally with "ALW". - Example: Shift schedule in a sequence of 3 and additionally a fax to the exchange centre, which is always to be sent.
Configuration 4.7 Message Services List box "Messaging services" • ▫ D1 SMS ▫ D2 SMS (Vodafone) ▫ E+ SMS ▫ FAX ▫ E-mail ▫ VOICE Use the NEW button to create a new messaging service. • An unambiguous name must be specified. Name • The name of the messaging service can be changed. • Max. 8 characters (no letters with accents). Protocol • Transfer protocol • Max. 8 characters Text length • Maximum length of the message text • Max. 160 characters; for pagers only 80 characters permitted.
Configuration Country code • A prefix placed in front of the actual target number of the recipient for this messaging service. • Leading zeros in the number of the recipient are omitted, for example, country code = 0049 target number = 0171 1234567; in this case, the message is sent to 0049171 1234567. • It is recommended to use the syntax 0049, 0041... . • The country prefix can also be entered directly in the target number of the recipient (menu option "Messages"). • Max.
Configuration The messaging service "E-mail" requires an e-mail account, see Section 4.9. NOTE If you select E-mail, a link is displayed to another menu option where you can make further settings required for this messaging service. Further settings ISP • For selecting an Internet service provider which has been set up under IPS settings, see Section 4.8. Host name • A name that identifies the device; can be selected freely.
Configuration SMTP server/IP • Server via which the e-mail is to be sent • This server is bound to the e-mail account. • Either a server name or an IP address can be specified; syntax: aaa.bbb.ccc.ddd, for example 213.165.64.20 These data are provided by your e-mail provider. • This server can be compared with the posting box used to send conventional letters. Authentication • Most e-mail providers require an authentication to send e-mails via an SMTP server.
Configuration POP Server IP • Inbox server of your e-mail account • This server can be compared with the letter box for receiving conventional letters. User ID • The user name or, for example, the customer number of your email account. Password • The password that is used for access to the inbox or for the SMTP authentication. Password confirmation • 4.8 A confirmation (input repetition) of your password to avoid incorrect inputs.
Configuration An e-mail is always sent via the Internet. To this end, an Internet Service Provider must be configured through which access to the Internet is possible from a mobile wireless device. There are call-by-call providers allowing this access; furthermore, all mobile service providers offer their own Internet access (see your Mobile Service Agreement).
Configuration DNS1 • Optional DNS (Domain Name Server) Syntax: e.g. 217.237.151.97 • Normally, no entry is necessary, since the settings are transferred by the ISP. • Even if a DNS is received by the ISP, it is not this entry which is used, but that of the ISP. DNS2 • Optional DNS (Domain Name Server) Notification: e.g. 217.237.151.97 • Normally, no entry is necessary, since the settings are transferred by the ISP.
Configuration 4.9 Function control The IE-GPRS-I/O can issue a cyclic message (sign of life) as a function monitoring signal. Text • Enter the text you wish to be displayed in the message in the text field, for example " Fault: Pump1". ▫ The maximum length permitted, including all text blocks, is 160 characters. Longer texts are truncated. It is possible to use text blocks to create a message text dynamically, see Section 4.6 Alarm Message. Target • Two targets can be specified.
Configuration • ; ACKN If acknowledgement is possible for this messaging service (menu option "Messaging services"), this feature can be activated here. • ; ALW • ▫ The message targets form a message sequence, in other words: If a target of this sequence was informed successfully (including acknowledgement), the message sequence is cancelled. ▫ If, however, a message target is to be informed in all cases, this target can be marked under "ALW".
Configuration 4.10 Server The Internet exchange server is operated with further partners on behalf of Weidmüller. The server is a relational database which can be accessed externally via SQL queries. The server itself need not be configured externally by the customer. To be able to use the server, only the following settings are required: Interconnection between two or several IE-GPRS-I/Os to one another can only be provided via the exchange server.
Configuration Server • • Server name ▫ Can be resolved via DNS or ▫ Server IP address If both are entered, an attempt is made first to reach the server via its server name. ID • Each IE-GPRS-I/O must contain an unambiguous name for identification within a group. Observe use of uppercase/lowercase letters! Password • Password for identification Observe use of uppercase/lowercase letters! Group • Communication group to which the IE-GPRS-I/O is to belong.
Configuration Mode • Master: Master IE-GPRS-I/O talks -> all slaves listen • Slave: Slave IE-GPRS-I/O talks -> only the master listens • Master/slave: Listens to everybody Connect automatically • If Connect automatically is enabled, the IE-GPRS-I/O attempts to establish the connection to the exchange server automatically after a reset. Send all input states • Time interval at which the IE-GPRS-I/O sends its input status to the exchange server ▫ 0 means that the input status is sent not cyclically.
Configuration 4.12 Logbook The IE-GPRS-I/O manages a logbook where important events, messages etc. are entered. Max. 255 entries are possible. If this number is exceeded, the oldest entries are overwritten. The entries can be viewed and deleted under the menu option "Logbook". Normally, the log file need not be reset. The entries are displayed in the form "Weekday", "Date", "Time", "Event" and "Error code".
Configuration 4.13 Cost control The IE-GPRS-I/O monitors the data volume for GPRS connections and the online time for GSM connections. To this end, you must enter the specifications from your mobile subscriber agreement in the menu Cost control. Rounding error • Each time a connection is established to the GPRS network, the provider debits a certain data volume from you at a flat rate. The amount of this value depends on the appropriate mobile subscriber agreement.
Configuration Limit value • Byte counter The following limit values can be set for two graduated report messages. Example: • ▫ If a volume tariff of 10 MB/month was agreed with the mobile service provider, with byte counter1 = 5 MB, a report message is issued when half of this volume has been used, and with byte counter2 = 8 MB again at 80 %. The setting is made in the menu "Messages", see Section 4.6 Alarm Message.
Configuration 4.14 Troubleshooting 4.15 Systemtime When the IE-GPRS-I/O starts an Internet connection (e.g. for sending an e-mail), it can match its system clock with a time server (SNTP server) on the Internet. Summer time • Summer/winter time is observed when setting the clock.
Configuration SNTP server • IP address or host name of the time server Default setting: Time server 1 of PTB in Braunschweig • Time zone in which the IE-GPRS-I/O is located (Germany +1) • If "Set clock" is set, the time match is performed when the Internet connection is first established. The internal clock is backed up for approx. 75 hours. If the IE-GPRS-I/O remains without operating voltage for longer, the clock must be reset via the time server. ATTENTION 4.
Hardware 5 Hardware 5.1 Installation This chapter provides all relevant information on the dimensions. 5.1.
Hardware 5.1.2 Installing the top-hat rail The IE-GPRS-I/O can be fastened on a top-hat rail which complies with the standard EN 50022: 1 35 7,5 This top-hat rail must be fastened on the control cubicle wall such that a conductive connection is provided. Observe the instructions of the manufacturer with reference to fastening. NOTE Installation Pull the top-hat rail downwards, at the same time pushing the device back onto the top-hat rail.
Hardware 5.1.3 Wall mounting There are two mounting plates intended for mounting of the device on the wall. The mounting plates are fastened with screws on the rear side of the housing and must be mounted as shown in the illustration. The top-hat rail adapter must be removed if you mount the device on the wall.
Hardware When mounting a top-hat rail adapter on the rear of the housing, it is imperative to observe the correct position of the retaining spring: NOTE Plastic variant: Retaining spring at the bottom Aluminium variant: Retaining spring at the top CAUTION: Incorrect mounting will reduce the retaining force of the top-hat rail adapters. Only use the original screws of the top-hat rail; longer screws will damage the electronics of your IE-GPRS-I/O.
Hardware 5.2 Installation notes Make sure that at least 35 mm of space is left above the module. A space of 35 mm must be provided beneath the module for routing of the cables for the interfaces and for the power supply. 5.2.1 Functional earthing For functional earthing, connect the "Functional earthing" terminal on the housing of the IE-GPRS-I/O to the equipotential bonding of the control cabinet. The connection "Functional earth" serves for purely operational functions (modem function).
Hardware 5.3 Installation guidelines The specified maximum operating temperature pertains to the air temperature beneath the IE-GPRS-I/O (air inlet). Observe a sufficient distance to devices emitting strong electromagnetic radiation (such as frequency converters, transformers, motor controllers, etc.). The clearance between these devices and the IE-GPRS-I/O should be as large as possible. If necessary install a shielding of partition walls (MU metal).
Hardware 5.6 Status display Three LEDs are located on the front panel of the IE-GPRS-I/O to display the operating status. To display the status of the port, 12 further LEDs are installed on the upperside/underside of the device to display the states of the digital inputs/outputs.
Hardware 5.6.1 Display "POWER on/off" LED Description OFF The supply voltage is turned off. Lights red Insufficient power supply The IE-GPRS-I/O is not ready for operation. Lights green The supply voltage is turned on. 5.6.
Hardware 5.6.4 "Ports" display LED 1 … 4 Digital inputs DI1 ...
Hardware 5.7 Connections / interfaces The connection for the power supply, the serial interface RS232, the connection for the external aerial and the slot for the telephone card are located on the front panel of the IE-GPRS-I/O: Aerial connection for the FME connector Plug-in SIM card RS232 interface Sub-D female socket connector Power supply 5.7.1 Power supply The IE-GPRS-I/O can be supplied either with +10 … 36 VDC or with 8 … 24 VAC. The power consumption is approx. 5 W.
Hardware Power supply connection The Alarm Modem IE-GPRS-I/O must only be connected to the electrical supply system by an electrical expert. DANGER The power supply of the Alarm Modem IE-GPRS-I/O must be provided exclusively by a power pack which complies with DIN EN 60 742 (VDE 0551). Make sure that an appropriate fuse is installed in the incoming supply feeder. 5.7.
Hardware Pin assignment of the terminals on the device underside GND Digital earth signal digital in 1 … 4 GND 1 DI1 0 ... 30 V DC signal digital in 1 2 DI2 0 ... 30 V DC signal digital in 2 3 DI3 0 ... 30 V DC signal digital in 3 4 DI4 0 ... 30 V DC signal digital in 4 Signal digital GND digital in 1 … 4 GND GND 5 DO1.1 0 ... 30 V DC signal digital out 1 5 DO1.2 0 ... 30 V DC signal digital out 1 6 DO2.1 0 ... 30 V DC signal digital out 2 6 DO2.2 0 ...
Hardware Pin assignment of the terminal on the device upperside GND GND3 Digital earth signal digital in 5 … 8 GND 7 DI5 0 ... 30 V DC signal digital in 5 8 DI6 0 ... 30 V DC signal digital in 6 9 DI7 0 ... 30 V DC signal digital in 7 10 DI8 0 ... 30 V DC signal digital in 8 GND GND3 Signal digital GND digital in 5 … 8 GND 11 DO3.1 0 ... 30 V DC signal digital out 3 11 DO3.2 0 ... 30 V DC signal digital out 3 12 DO4.1 0 ... 30 V DC signal digital out 4 12 DO4.2 0 ...
Hardware Settings of the analog inputs 1 2 3 4 Connection of voltage sensors 0 … 10 V OFF OFF ON Connection of current sensors 0 … 20 mA OFF ON Connection of resistance thermometers PT1000 OFF 1 2 3 4 OFF OFF ON OFF ON OFF 1 2 3 4 ON Connection of voltage sensors 0 … 10 V Connection of current sensors 0 … 20 mA Connection of resistance thermometers PT1000 AI1 - Analog input 3 Connection of current sensors 0 … 20 mA OFF ON Connection of resistance thermometers PT1000 OFF 2 AI1 - Analog
Technical Data 6 Technical Data Type Designation Alarm Modem Art. no.
Technical Data Electrical Data Power supply Rated operating voltage Rated operating capacity Fuse, external Rated frequency Redundancy Inputs/outputs Digital inputs - Input voltage range Digital outputs - Output voltage range Analog inputs - Input voltage range - Input current range - Temperature RS232 Wireless General specifications Error messages The power supply of the IE-GPRS-I/O must be provided exclusively by a power pack which complies with DIN EN 60742 or VDE 0551.
Standards and Certifications 7 Standards and Certifications 7.1 Harmonised standards EN 50081-1 Noise emission for residential, commercial and lightindustrial environment EN 61000-6-2 Noise immunity for the industrial environment 7.2 Certification to DIN EN ISO 9001 The Weidmüller Interface GmbH & Co. KG is certified to ISO 9001. 7.3 Approbations 7.
Symbols Used 8 Symbols Used Connection for the functional earthing Mains transformer d.c.
Glossary 9 Glossary This chapter provides a list of all abbreviations and special terms used in this Manual with their meanings. A • AT commands The term 'AT commands' is used for the commands that were originally used by the company Hayes and thus have become quasi-standard for configuring and parameterising modems. • DNS The Domain Name System (DNS) is one of the most important services on the Internet. The DNS is a distributed database that manages the name space on the Internet.
Glossary • Dynamic IP IP address, is assigned to the client from a defined address range dynamically, e.g. via a DHCP server. • Fixed IP Fixed IP addresses are assigned statically to the client by the appropriate Internet provider. • GSM The Global System for Mobile Communications (GSM) is a fully digital mobile communication network standard that is used mainly for telephony, but also for line-switched and packet-switched data transfer and for short messages (SMS).
Glossary M N O P • Private IP Private IP addresses or private networks are IP addresses/subnets that can be used for any purpose and by everybody. However, they are not routed on the Internet. • POP3 Address of the Internet service provider for fetching e-mails • PPP Point to Point Protocol.
Glossary T • TCP The Transmission Control Protocol (TCP) is a reliable, connectionoriented transfer protocol in computer networks. It is part of the TCP/IP protocol family. TCP provides a virtual channel between two computers (more exactly: the end points (sockets) of two applications on these computers). Data can be transferred on this channel in both directions. In the most cases, TCP is based on the IP protocol. • UDP The User Datagram Protocol (UDP) is a minimum network protocol without connection.
9-92