Data sheet
Automation Products - u-remote IP20
UR20-4DI-4DO-PN-FSOE-V2
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date 21 March 2019 15:58:19 CET
Catalogue status 15.03.2019 / We reserve the right to make technical changes. 3
General data
Air humidity (operation) 10% to 95%, non-
condensing as per DIN EN
61131-2
Air humidity (storage) 10% to 95%, non-
condensing as per DIN EN
61131-2
Air humidity (transport) 10% to 95%, non-
condensing as per DIN EN
61131-2
Air pressure (operation)
≥ 795 hPa (height ≤ 2000
m) as per DIN EN 61131-2
Air pressure (storage) 1013 hPa (height 0 m) to
700 hPa (height 3000 m)
as per DIN EN 61131-2
Air pressure (transport) 1013 hPa (height 0 m) to
700 hPa (height 3000 m)
as per DIN EN 61131-2
Pollution severity
2
Shock 15 g over 11 ms, half
sinus wave, acc. to IEC
60068-2-27
Surge voltage category II
Test voltage 500 V
UL 94 flammability rating
V-0
Vibration resistance 5 Hz ≤ f ≤ 8.4 Hz: 3.5
mm amplitude as per IEC
60068-2-6, 8.4 Hz ≤ f ≤
150 Hz: 1 g acceleration
as per IEC 60068-2-6
Power supply
Current consumption from I
IN
(power
segment of the field bus coupler), typ. 8 mA
Current consumption from I
OUT
(the
respective power segment) 30 mA
Reverse polarity protection
Yes
Voltage supply 24 V DC +20%/ -15%, via
the system bus
Safety-related data
MTTF
100 Years
Proportion of safety-related outages
(SFF) 98 %
System data
Field bus protocol
EtherCAT
Galvanic isolation 500 V DC between the
current paths
Interface
u-remote system bus
Module type Safe input and output
module
Possible connection 2 conductor, 4 conductors
Transmission speed of system bus, max. 48 Mbit
Classifications
ETIM 6.0 EC001597
eClass 6.2 27-24-26-10
eClass 9.0 27-24-26-02
eClass 9.1 27-24-26-02
Approvals
Approvals
ROHS Conform