Data Sheet
Data sheet
OMNIMATE Power - series WGK
WGK 50 VP/Z GY BX
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date May 27, 2019 2:21:51 PM CEST
Catalogue status 23.05.2019 / We reserve the right to make technical changes. 2
Dimensions and weights
Net weight 81.4 g
System parameters
Product family OMNIMATE Power - series
WGK
Wire connection method Cable lug: ring cable /
spade lug
Conductor outlet direction 180°
Fitted by customer Yes
Screwdriver blade 1.2 x 6.5
Tightening torque, min. 4 Nm
Tightening torque, max. 8 Nm
Clamping screw M 6
Stripping length
24 mm
Touch-safe protection acc. to DIN VDE
0470 IP 20
Material data
Insulating material Wemid (PA)
Colour grey
Colour chart (similar) RAL 7035
UL 94 flammability rating V-0
Contact material E-Cu
Contact surface tinned
Storage temperature, min. -25 °C
Storage temperature, max. 55 °C
Max. relative humidity during storage 80 %
Operating temperature, min. -50 °C
Operating temperature, max. 120 °C
Temperature range, installation, min.
-25 °C
Temperature range, installation, max. 120 °C
Conductors suitable for connection
Clamping range, min. 10 mm²
Clamping range, max. 50 mm²
Wire connection cross section AWG,
min.
AWG 6
Wire connection cross section AWG,
max.
AWG 1/0
Solid, min. H05(07) V-U 16 mm²
Solid, max. H05(07) V-U 50 mm²
Stranded, min. H07V-R 16 mm²
Stranded, max. H07V-R 50 mm²
Flexible, min. H05(07) V-K 16 mm²
Flexible, max. H05(07) V-K 50 mm²
w. wire end ferrule, DIN 46228 pt 1, min10 mm²
w. wire end ferrule, DIN 46228 pt 1,
max.
50 mm²
Clampable conductor
Cross-section for conductor connection Type
fine-wired
nominal
35 mm²
AEH Stripping length nominal
25 mm
Max. clamping range 50 mm²
Rated data acc. to IEC
tested acc. to standard
IEC 60664-1, IEC 61984
Rated current, min. no. of poles
(Tu=20°C) 150 A
Rated current, max. no. of poles
(Tu=20°C) 150 A
Rated voltage for surge voltage class /
pollution degree III/3
690 V
Rated impulse voltage for surge voltage
class/ contamination degree III/3 6 kV