Datasheet
Data sheet
OMNIMATE Signal - series BL/SL 5.08
BLZP 5.08HC/11/180 SN OR BX
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date 16 January 2020 11:20:49 CET
Catalogue status 13.01.2020 / We reserve the right to make technical changes. 3
Plug gauge in accordance with EN
60999 a x b; ø
2.8 mm x 2.4 mm
Clampable conductor
Cross-section for conductor connection Type fine-wired
nominal 0.5 mm²
wire end ferrule Stripping length nominal 6 mm
Recommended wire-
end ferrule
H0,5/6
Cross-section for conductor connection Type fine-wired
nominal 1 mm²
wire end ferrule Stripping length nominal 6 mm
Recommended wire-
end ferrule
H1,0/6
Cross-section for conductor connection Type fine-wired
nominal 1.5 mm²
wire end ferrule Stripping length nominal 7 mm
Recommended wire-
end ferrule
H1,5/7
Cross-section for conductor connection Type fine-wired
nominal 2.5 mm²
wire end ferrule Stripping length nominal 7 mm
Recommended wire-
end ferrule
H2,5/7
Reference text The outside diameter of the plastic collar should not be larger than the pitch (P)., Length of ferrules
is to be chosen depending on the product and the rated voltage.
Max. clamping range 4 mm²
Rated data acc. to IEC
tested acc. to standard
IEC 60664-1, IEC 61984
Rated current, min. number of poles
(Tu=20°C) 23 A
Rated current, max. number of poles
(Tu=20°C) 18 A
Rated current, min. number of poles
(Tu=40°C) 21 A
Rated current, max. number of poles
(Tu=40°C) 16 A
Rated voltage for surge voltage class /
pollution degree II/2 400 V
Rated voltage for surge voltage class /
pollution degree III/2 320 V
Rated voltage for surge voltage class /
pollution degree III/3 250 V
Rated impulse voltage for surge voltage
class/ pollution degree II/2 4 kV
Rated impulse voltage for surge voltage
class/ pollution degree III/2 4 kV
Rated impulse voltage for surge voltage
class/ contamination degree III/3 4 kV
Short-time withstand current resistance
3 x 1s with 120 A
Rated data acc. to CSA
Institute (CSA)
Certificate No. (CSA)
200039-1121690
Rated voltage (Use group B / CSA) 300 V
Rated voltage (Use group C / CSA) 50 V
Rated voltage (Use group D / CSA) 300 V
Rated current (Use group B / CSA) 20 A
Rated current (Use group D / CSA) 20 A
Wire cross-section, AWG, min. AWG 30
Wire cross-section, AWG, max.
AWG 12
Reference to approval values Specifications are
maximum values, details -
see approval certificate.