Datasheet
Data sheet
OMNIMATE Signal - series BL/SL 5.08
BLZP 5.08HC/10/180 SN OR BX
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date November 28, 2019 9:10:13 AM CET
Catalogue status 22.11.2019 / We reserve the right to make technical changes. 3
Plug gauge in accordance with EN
60999 a x b; ø
2.8 mm x 2.4 mm
Clampable conductor
Cross-section for conductor connection Type fine-wired
nominal 0.5 mm²
wire end ferrule Stripping length nominal 6 mm
Recommended wire-
end ferrule
H0,5/6
Cross-section for conductor connection Type fine-wired
nominal 1 mm²
wire end ferrule Stripping length nominal 6 mm
Recommended wire-
end ferrule
H1,0/6
Cross-section for conductor connection Type fine-wired
nominal 1.5 mm²
wire end ferrule Stripping length nominal 7 mm
Recommended wire-
end ferrule
H1,5/7
Cross-section for conductor connection Type fine-wired
nominal 2.5 mm²
wire end ferrule Stripping length nominal 7 mm
Recommended wire-
end ferrule
H2,5/7
Reference text The outside diameter of the plastic collar should not be larger than the pitch (P).
Max. clamping range 4 mm²
Rated data acc. to IEC
tested acc. to standard
IEC 60664-1, IEC 61984
Rated current, min. number of poles
(Tu=20°C) 23 A
Rated current, max. number of poles
(Tu=20°C) 18 A
Rated current, min. number of poles
(Tu=40°C) 21 A
Rated current, max. number of poles
(Tu=40°C) 16 A
Rated voltage for surge voltage class /
pollution degree II/2 400 V
Rated voltage for surge voltage class /
pollution degree III/2 320 V
Rated voltage for surge voltage class /
pollution degree III/3 250 V
Rated impulse voltage for surge voltage
class/ pollution degree II/2 4 kV
Rated impulse voltage for surge voltage
class/ pollution degree III/2 4 kV
Rated impulse voltage for surge voltage
class/ contamination degree III/3 4 kV
Short-time withstand current resistance
3 x 1s with 120 A
Rated data acc. to CSA
Institute (CSA)
Certificate No. (CSA)
200039-1121690
Rated voltage (Use group B / CSA) 300 V
Rated voltage (Use group C / CSA) 50 V
Rated voltage (Use group D / CSA) 300 V
Rated current (Use group B / CSA) 20 A
Rated current (Use group D / CSA) 20 A
Wire cross-section, AWG, min. AWG 30
Wire cross-section, AWG, max.
AWG 12
Reference to approval values Specifications are
maximum values, details -
see approval certificate.