Datasheet
Data sheet
W-Series
WPE 50N
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date February 4, 2015 8:06:26 AM CET
Catalogue status xx.xx.xxxx / We reserve the right to make technical changes. 2
Dimensions and weights
Width 18.5 mm
Height 71 mm
Depth 69.6 mm
Net weight 126.143 g
Temperatures
Continuous operating temp., min. -50 °C
Continuous operating temp., max. 120 °C
Additional technical data
Explosion-tested version Yes
Installation advice Screwed
Number of similar terminals 1
Open sides closed
Type of mounting
Screwed
Version Screw connection, With PE
connection, closed
CSA ratings data
Certificate No. (CSA) 200039-1057876
Wire cross section max. (CSA)
0 AWG
Wire cross section min. (CSA) 14 AWG
Clampable wires (rated connection)
Type of connection Screw connection
Stripping length 24 mm
Blade size S4 (DIN 6911)
Connection direction on side
Number of connections 2
Clamping range, rated connection, min. 5.26 mm²
Clamping range, rated connection, max. 70 mm²
Clamping screw M 6
Tightening torque, min. 4 Nm
Tightening torque, max. 6 Nm
Gauge to IEC 60947-1
B10
Wire connection cross section, solid
core, min. rated connection 10 mm²
Wire connection cross section, solid
core max. rated connection 16 mm²
Wire connection cross section, stranded,
rated connection, min. 10 mm²
Wire connection cross section, stranded,
rated connection, max. 70 mm²
Wire connection cross section, finely
stranded, max. 50 mm²
Wire connection cross-section, finely
stranded, min.
10 mm²
Wire connection cross section, finely
stranded with wire-end ferrules DIN
46228/1, rated connection, min. 10 mm²
Wire connection cross section, finely
stranded with wire-end ferrules DIN
46228/1, rated connection, max. 50 mm²
Wire connection cross section AWG,
min.
AWG 14
Wire connection cross section AWG,
max. AWG 0
Rated data
Rated cross-section 50 mm²
Rated voltage to adjoining terminal 1,000 V
Rated impulse withstand voltage to
adjacent terminal 8 kV
Standards
IEC 60947-7-2
Pollution severity 3
UL ratings data
Certificate No. (UR) E60693
Conductor size Factory wiring max. (UR) 0 AWG
Conductor size Factory wiring min. (UR) 10 AWG
Conductor size Field wiring max. (UR) 0 AWG