Datasheet
Data sheet
W-Series
WPE 1.5/R3.5
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date November 28, 2019 9:11:30 AM CET
Catalogue status 22.11.2019 / We reserve the right to make technical changes. 3
Conductors for clamping (rated connection)
Blade size 0.4 x 2.5 mm
Clamping range, max. 1.5 mm²
Clamping range, min. 0.13 mm²
Clamping screw M 2
Connection cross-section, stranded,
max. 1.5 mm²
Connection cross-section, stranded, min.
1.5 mm²
Connection direction on side
Gauge to IEC 60947-1 A1
Number of connections 2
Stripping length 7 mm
Tightening torque, min. 0.3 Nm
Type of connection Screw connection
Wire connection cross section AWG,
max. AWG 16
Wire connection cross section AWG,
min. AWG 26
Wire connection cross section, finely
stranded, max.
1.5 mm²
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/1, max. 1.5 mm²
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/1, min. 0.5 mm²
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, max. 0.5 mm²
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, min. 0.5 mm²
Wire connection cross-section, finely
stranded, min.
0.5 mm²
Wire connection cross-section, solid
core, max. 1.5 mm²
Wire connection cross-section, solid
core, min. 0.5 mm²
Dimensions
TS 15 offset 13.5 mm
PE rating data
Rated short-time current 180 A (1.5 mm²)
PEN function No
Rating data
Rated cross-section 1.5 mm²
Rated voltage to adjoining terminal 400 V
Standards
IEC 60947-7-2
Volume resistance according to IEC
60947-7-x 1.83 mΩ
Power loss in accordance with IEC
60947-7-x 0.56 W
Rated impulse withstand voltage
4 kV
Rated impulse withstand voltage to
adjacent terminal 6 kV
Pollution severity
3
UL rating data
Certificate No. (UR) E60693
Conductor size Factory wiring max. (UR) 18 AWG
Conductor size Factory wiring min. (UR) 26 AWG
Conductor size Field wiring max. (UR)
18 AWG
Conductor size Field wiring min. (UR) 26 AWG
Classifications
ETIM 6.0 EC000901
ETIM 7.0 EC000901
eClass 9.0 27-14-11-41
eClass 9.1 27-14-11-41
eClass 10.0 27-14-11-41
UNSPSC 30-21-18-11