Datasheet
Data sheet
PROmax
PRO MAX 70W 5V 14A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date February 24, 2015 9:25:49 AM CET
Catalogue status 23.01.2015 / We reserve the right to make technical changes. 3
EMC / shock / vibration
Vibration resistance IEC 60068-2-6
2.3 g
Interference immunity test acc. to EN 55024, EN 55022,
IEC61000-3-2,-3,
IEC61000-4-2,-3,-4,-5,-6,-8,-11
Shock resistance IEC 60068-2-27 30 g in all directions
Insulation coordination
Class of protection I, with PE connection
Humidity at operating temperature 5...95 %, no condensation
Insulation voltage input / earth 3.5 kV
Insulation voltage output / earth 0.5 kV
Insulation voltage, input/output 4 kV
Pollution severity
2
Surge voltage category III
Electrical safety (applied standards)
Electrical machine equipment
Acc. to EN60204
For use with electronic equipment Acc. to EN50178 /
VDE0160
Protection against dangerous shock
currents Acc. to VDE0106-101
Protective separation / protection
against electrical shock
VDE0100-410 / acc. to
DIN57100-410
Safety extra-low voltage SELV acc. to EN60950,
PELV acc. to EN60204,
IEC61204
Safety transformers for switch-mode
power supplies
IEC61558-2-16
Connection data (input)
Conductor cross-section, AWG/kcmil ,
max. 10
Conductor cross-section, AWG/kcmil ,
min. 26
Conductor cross-section, flexible , min. 0.22 mm²
Conductor cross-section, rigid , max. 6 mm²
Conductor cross-section, rigid , min. 0.18 mm²
Connection system [Input] Screw connection
Number of terminals [Input] 3 for L/N/PE
Screwdriver blade 0.8 x 4.0, PZ 1
Tightening torque, max. 0.6 Nm
Tightening torque, min.
0.5 Nm
Wire connection cross section, flexible
(input), max. 4 mm²
Connection data (output)
Conductor cross-section, AWG/kcmil ,
max. 12
Conductor cross-section, AWG/kcmil ,
min. 26
Conductor cross-section, flexible , max. 4 mm²
Conductor cross-section, flexible , min. 0.5 mm²
Conductor cross-section, rigid , max. 6 mm²
Conductor cross-section, rigid , min. 0.5 mm²
Connection system [Output] Screw connection
Number of terminals [Output] 8 (++,---,11,13,14)
Screwdriver blade 0.6 x 3.5
Tightening torque, max.
0.6 Nm
Tightening torque, min. 0.5 Nm
Signalling
Contact load (NO contact) max. 30 V DC / 1 A
Floating contact
Yes
Status indication LED red/green and relay
(≥21.6 V DC LED green,
relay on/ ≤20.6 LED red,
relay off)