Datasheet

Data sheet
PROmax
PRO MAX 70W 5V 14A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date February 24, 2015 9:25:49 AM CET
Catalogue status 23.01.2015 / We reserve the right to make technical changes. 2
Dimensions and weights
Width 32 mm
Height 130 mm
Depth 125 mm
Net weight 650 g
Temperatures
Humidity at operating temperature 5...95 %, no condensation
Operating temperature
-25 °C...70 °C
Storage temperature -40 °C...85 °C
Input
AC current consumption 1 A @ 230 V AC / 1.5 A @
115 V AC
AC input voltage range
85…277 V AC
Connection system [Input]
Screw connection
DC current consumption 1A @ 370 VDC / 1,5A @
120 VDC
DC input voltage range 80...370 V DC
Frequency range AC 45…65 Hz
Input fuse (internal) Yes
Inrush current max. 15 A
Rated input voltage
100...240 V AC (wide-
range input)
Recommended back-up fuse 6 A, Char. B, circuit
breaker, 3 - 5 A Char. C,
circuit breaker
output
Connection system [Output]
Screw connection
Continuous output current @ U
Rated
16,8 A @ 45°C, 10,5 A @
70°C
Output voltage 4.5...7 V (adjustable via
potentiometer)
Parallel connection option
yes, max. 5
Power boost @ U
Rated
16.8 A (1 min), 21 A (4s)
Pulsed current capacity @ U
Rated
42 A (2ms)
Rated (nominal) output current @ U
Nom
14 A @ 60°C
Rated output voltage
5 V DC
Residual ripple, breaking spikes < 50 mVss @ U
Nenn
, Full
Load
General data
AC failure bridging time @ I
Nom
min. 20 ms
Current limiting > 120 % I
N
Degree of efficiency 86%
Derating > 60°C / 75% @ 70°C
Earth leakage current, max. 3.5 mA
Housing version Metal, corrosion resistant
MTBF
>500.000h (25°C, IEC
61709)
Mounting position, installation notice Horizontal on TS35
mounting rail, with 50 mm
of clearance at top and
bottom for air circulation.
Can be mounted side
by side with no space in
between.
Operating temperature -25 °C...70 °C
Power factor (approx.) > 0.90 @ 230 V AC
Power loss, idling 1 W
Power loss, nominal load 11.7 W
Protection against reverse voltages from
the load > 7.5 V DC
Series switching capability
Yes
Start-up
≥ -40 °C
Status indication LED red/green and relay
(≥21.6 V DC LED green,
relay on/ ≤20.6 LED red,
relay off)
Surge voltage category III