Datasheet

Data sheet...
Series B2C/S2C 3.50 - 2-row
B2CF 3.50/04/180F SN OR BX
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date October 10, 2012 8:30:58 AM CEST
Catalogue status xx.xx.xxxx / We reserve the right to make technical changes. 2
Dimensions and weights
Net weight 3.132 g
System parameters
Product family Series B2C/S2C 3.50 - 2-
row
Conductor connection system PUSH IN spring
connection
Outgoing direction of conductor 180°
Pitch in mm (P) 3.5 mm
Pitch in inches (P) 0.138 inch
No. of poles 4
Number of rows 1
Stripping length 10 mm
L1 in mm 3.5 mm
L1 in inches 0.138 inch
Touch-safe protection acc. to DIN VDE
0470 IP 20
Touch-safe protection acc. to DIN VDE
57 106 Safe from finger touch
Material data
Insulating material PA 66 GF 30
Colour Orange
Colour chart (similar) RAL 2000
UL 94 flammability rating V-0
CTI ≥ 600
Contact material Copper alloy
Contact surface tinned
Continuous operating temp., min.
-25 °C
Continuous operating temp., max. 120 °C
Connectable conductors
Clamping range, rated connection, min. 0.14 mm²
Clamping range, rated connection, max. 1.5 mm²
Solid, min. H05(07) V-U 0.14 mm²
Solid, max. H05(07) V-U 1.5 mm²
Flexible, min. H05(07) V-K 0.14 mm²
Flexible, max. H05(07) V-K 1.5 mm²
w. wire end ferrule, DIN 46228 pt 1, min
0.14 mm²
w. wire end ferrule, DIN 46228 pt 1,
max. 1.5 mm²
w. plastic collar ferrule, DIN 46228 pt 4,
min. 0.14 mm²
w. plastic collar ferrule, DIN 46228 pt 4,
max. 1 mm²
DIN IEC rating data
Rated current, min. no. of poles
(TU=20°C) 13.4 A
Rated current, max. no. of poles
(Tu=20°C) 10 A
Rated current, number of poles
(Tu=40°C), min 12 A
Rated current, number of poles
(Tu=40°C), max. 9 A
Rated voltage for surge voltage class /
pollution degree II/2 320 V
Rated voltage for surge voltage class /
pollution degree III/2 160 V
Rated voltage for surge voltage class /
pollution degree III/3 160 V
Rated impulse voltage for surge voltage
class/ pollution degree II/2 2.5 kV
Rated impulse voltage for surge voltage
class/ pollution degree III/2 2.5 kV
Rated impulse voltage for surge voltage
class/ contamination degree III/3
2.5 kV
Short-time withstand current resistance 3 x 1s with 80 A
CSA rating data
Rated voltage (Use group B) 300 V
Rated current (use group B) 5 A
Wire cross-section, AWG, min. AWG 26
Wire cross-section, AWG, max. AWG 16
UL 1059 rating data
Rated voltage (use group B) 300 V
Rated current (use group B) 10 A
Rated voltage (use group C) 50 V
Rated current (use group C) 10 A
Rated voltage (use group D) 300 V
Rated current (use group D) 10 A
Wire cross-section, AWG, min. AWG 26
Wire cross-section, AWG, max. AWG 16