Datasheet

Data sheet
ACT20M
ACT20M-AI-AO-S
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date January 24, 2020 3:24:54 PM CET
Catalogue status 13.01.2020 / We reserve the right to make technical changes. 2
Dimensions and weights
Width 6.1 mm
Width (inches) 0.24 inch
Height 112.5 mm
Height (inches) 4.429 inch
Depth 114.3 mm
Depth (inches)
4.5 inch
Net weight 80 g
Temperatures
Humidity 40 °C / 93 % rel. humidity,
no condensation
Operating temperature, max.
70 °C
Operating temperature, min. -25 °C
Storage temperature, max. 85 °C
Storage temperature, min. -40 °C
Operating temperature -25 °C...70 °C
Ambient temperature -25 °C...+70 °C
Storage temperature -40 °C...85 °C
Probability of failure
MTBF 231 Years
Environmental Product Compliance
REACH SVHC Lead 7439-92-1
Rated data UL
UL certificate E337701.pdf
Input
Number of inputs
1
Sensor Voltage source, Current
source, 2-wire transmitter
(without own power
supply)
Sensor supply
17…28 V DC (@ 20 mA)
Input voltage configurable, 0(2)…10 V,
0(1)…5 V
Input resistance, voltage
>500 kΩ
Input current configurable, 0...20 mA,
4…20mA
Voltage drop, current input <1,5 V
Input resistance, current
70 Ω
Voltage drop <1,5 V
Output
Number of outputs
1
Output voltage, note configurable, 0(2)...10 V,
0(1)...5 V
Output current configurable, 0...20 mA,
4...20 mA
Cut-off frequency (-3 dB)
100 Hz
load impedance voltage ≥ 10 kΩ
load impedance current ≤ 600 Ω, @ max 23mA
General data
Accuracy < 0.05 % of measuring
range
Configuration
DIP switch
Galvanic isolation 3-way isolator
Power consumption, max. 1.2 W
Power consumption, typ. 0.84 W
Rail TS 35
Step response time ≤ 7 ms
Temperature coefficient
≤ 0.01 % / °C
Voltage supply 24 V DC ± 30 %