Datasheet

Data sheet
W-Series
WTL 6/1
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date 11 March 2020 11:26:23 CET
Catalogue status 06.03.2020 / We reserve the right to make technical changes. 3
Conductors for clamping (rated connection)
Blade size 0.8 x 4.0 mm
Clamping range, max. 10 mm²
Clamping range, min. 0.5 mm²
Clamping screw M 3.5
Connection cross-section, stranded,
max. 10 mm²
Connection cross-section, stranded, min.
1.5 mm²
Connection direction on side
Gauge to IEC 60947-1 A5
Number of connections 2
Stripping length 12 mm
Tightening torque, max. 1.6 Nm
Tightening torque, min. 1 Nm
Torque level with DMS electric
screwdriver 3
Type of connection
Screw connection
Wire connection cross section AWG,
max. AWG 8
Wire connection cross section AWG,
min. AWG 20
Wire connection cross section, finely
stranded, max.
10 mm²
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/1, max. 6 mm²
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/1, min. 0.5 mm²
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, max. 6 mm²
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, min. 0.5 mm²
Wire connection cross-section, finely
stranded, min.
0.5 mm²
Wire connection cross-section, solid
core, max. 10 mm²
Wire connection cross-section, solid
core, min. 0.5 mm²
Disconnect terminals
Cross-disconnect without
Integral test socket No
Slitting sliding
Torque max. screw separator
0.7 Nm
Torque min. screw separator 0.5 Nm
Rating data
Rated cross-section 6 mm²
Rated voltage 630 V
Rated current 41 A
Current at maximum wires 57 A
Volume resistance according to IEC
60947-7-x 0.78 mΩ
Power loss in accordance with IEC
60947-7-x 1.31 W
Rated impulse withstand voltage 6 kV
Pollution severity 3
UL rating data
Certificate No. (UR) E60693
Conductor size Factory wiring max. (UR) 8 AWG
Conductor size Factory wiring min. (UR) 20 AWG
Conductor size Field wiring max. (UR) 8 AWG
Conductor size Field wiring min. (UR) 20 AWG
Current size C (UR)
45 A
Voltage size C (UR) 300 V
Classifications
ETIM 6.0 EC000902
ETIM 7.0 EC000902
eClass 9.0 27-14-11-26
eClass 9.1 27-14-11-26
eClass 10.0 27-14-11-26
UNSPSC 30-21-18-11