User Documentation

Weidmüller Interface GmbH Co. KG; Klingenbergstraße 16, 32758 Detmold-Germany
ZDK 2.5
ZDK 2.5 PE
440 V
20 A / ΔT 40 K
34,4 K / 20 A
20 A / ΔT 40 K
0,6 mΩ
1,0 mΩ
2,5 mm²
2,5 mm²
0,5 - 2,5 mm²
0,5 - 2,5 mm²
0,5 - 2,5 mm²
0,5 - 2,5 mm²
0,5 - 2,5 mm²
0,5 - 2,5 mm²
26 - 14 AWG
26 - 14 AWG
10 mm
10 mm
Application Case
352 V
352 V
352 V
352 V
275 V
E - Next to a protective conductor terminal (earth) without a end plate
352 V
IECEx / ATEX Terminal and Cross-Connection Arrangements:
- Conductor cross section flexible
- cross section, American Wire Gauge
- Stripping length
- Conductor cross section stranded
- Rated current
- Temperature rise with rated current
- Rated current with ZQV
- Rated voltage
T
echnical data according to IEC/EN 60079-7 (increased safety "eb"):
Max voltage data according to IEC/EN 60079-7 in conjunction with
protective earth terminal blocks of the ZDK PE-Series, (increased safety "eb"):
A - Continuos
C - Adjacent - separated by a end plate
D - Intermediate - briding one or more unconnected terminals (e.g. every 3rd terminal)
Information for further cross-connector arrangements will be provided on request.
- Contact resistance top level
with rated conductor, 2,5 mm²
- Rated conductor cross section
- Contact resistance bot level
with rated conductor, 2,5 mm²
- Conductor cross section solid
Version: ZDK 2.5-PE; 10248892 Index: 02 Date: 05.2019
2