User Documentation

Weidmüller Interface GmbH Co. KG; Klingenbergstraße 16, 32758 Detmold-Germany
WDU 6
WPE 6
690 V
220 V
41 A / ΔT 40 K
34,5 K / 41 A
41 A / ΔT 40 K
0,18 mΩ 0,25 mΩ
6mm²
6mm²
0,14 - 6 mm²
0,14 - 6 mm²
0,14 - 6 mm²
0,14 - 6 mm²
0,14 - 6 mm²
0,14 - 6 mm²
26 - 10 AWG 26 - 10 AWG
0,5 - 2,5 mm²
---
0,8 - 1,6 Nm
0,8 - 1,3 Nm
0,5 - 1,0 Nm
0,5 - 1,0 Nm
12 mm
12 mm
IECEx / ATEX Terminal and Cross-Connector Arrangements:
A
C
D
E
H
A
C
D
E
440 V
440 V
176 V
352 V
H
176 V
Information for further cross-connector arrangements will be provided on request.
Continuous
Next to a protective conductor terminal (earth) without a partition plate
Adjacent – separated by a partition plate
Intermediate - bridging one or more unconnected terminals
Cross-connection with twin parallel
Technical data according to IEC/EN 60079-7 (increased safety "eb"):
- Rated current with WQV
- Rated voltage with rated cross section
- Rated current
- Temperature rise with rated current
- Rated voltage with LS 2.8
- Rated conductor cross section
- Conductor cross section solid
- Contact resistance
with rated conductor, 6,0mm²
- cross section, American Wire Gauge
- Conductor cross section stranded
- Conductor cross section flexible
- WDU 6 with WQV 6 220 V
- 2 conductors with same cross-section
- Tightening torque range, fixing screw
- Tightening torque range, terminal screw
- Tightening torque range for WQV…
Max voltage data with optional screen bus bar LS 2.5
Application Case
- Stripping length
Max voltage data according to IEC/EN 60079-7 in conjunction with
protective conductor terminal blocks of the WPE-Series, (increased safety "eb"):
Version: WDU/WPE 6 7799740 Index: 06 Date: 5.2019
2