User Documentation
Weidmüller Interface GmbH Co. KG; Klingenbergstraße 16, 32758 Detmold-Germany
WDU 4/ZZ
WPE 4/ZZ
690 V
29,5 A / ∆T 40 K
33,7 K / 29,5 A
29,5 A / ∆T 40 K
0,56 mΩ 0,58 mΩ
4 mm² 4 mm²
0,14 - 6 mm² 0,14 - 6 mm²
0,14 - 6 mm² 0,14 - 6 mm²
0,14 - 4 mm² 0,14 - 4 mm²
26 - 10 AWG 26 - 10 AWG
0,5 - 1,5 mm² 0,5 - 1,5 mm²
0,5 - 0,8 Nm 0,5 - 0,8 Nm
10 mm 10 mm
A
D
E
H
I
A  D  E  H
 440 V  352 V 440 V 275 V
I
88 V
Information for further cross-connector arrangements will be provided on request.
 - Stripping length
IECEx / ATEX Terminal and Cross-Connector Arrangements:
 - cross section, American Wire Gauge
 - Tightening torque range, terminal screw
Max voltage data according to IEC/EN 60079-7 in conjunction with
protective conductor terminal blocks of the WPE-Series, (increased safety "eb"): 
 - 2 conductors with same cross-section
 - Rated conductor cross section
 - Conductor cross section flexible 
 - Contact resistance
 with rated conductor, 4 mm² 
 - Conductor cross section stranded
 - Conductor cross section solid
 - Rated current with ZQV
 - Rated voltage
Technical data according to IEC/EN 60079-7 (increased safety "eb"):
 - Rated current
 - Temperature rise with rated current 
Application Case
Intermediate - bridging one or more unconnected terminals (e.g. every 3rd terminal)
Next to a protective conductor terminal (earth) without a partition plate
Cross-connection with triple parallel
Continuous
Cross-connection with twin parallel
Version: WDU/WPE 4/ZZ; 9936661 Index: 03 Date: 10.2018