Approval/Certificate/Document of Conformity

[13]
Schedule
[14] TYPE EXAMINATION CERTIFICATE No.
DEMKO 14 ATEX 1389U
Rev. 1
00-IC-F0061 Issue 12.0 This certificate may only be reproduced in its entirety and without any change, schedule included. Page 3 of 3
Electrical data
Model
Ratings
WMF 2.5 FU SW
250 V, 6.3 A
WMF 2.5 FU 10-36V SW
36 V, 6.3 A
WMF 2.5 FU 100-250V SW
250 V, 6.3 A
WMF 2.5 FU 60-150V SW
150 V, 6.3 A
WMF 2.5 FU 30-70V SW
70 V, 6.3 A
WMF 2.5 FU PE SW
250 V, 6.3 A
WMF 2.5 FU PE 10-36V SW
36 V, 6.3 A
WMF 2.5 FU PE 100-250V SW
250 V, 6.3 A
WMF 2.5 FU PE 60-150V SW
150 V, 6.3 A
WMF 2.5 FU PE 30-70V SW
70 V, 6.3 A
WSI 4
250 V, 6.3 A
WSI 4/LD 10-36V AC/DC
36 V, 6.3 A
WSI 4/LD 30-70V AC/DC
70 V, 6.3 A
WSI 4/LD 60-150V AC/DC
150 V, 6.3 A
WSI 4/LD 140-250V AC/DC
250 V, 6.3 A
WSI 6
500 V, 6.3 A
WSI 6/LD 250AC LLC
250 V, 6.3 A
WSI 6/LD 10-36V LLC
36 V, 6.3 A
WSI 6/LD 30-70V LLC
70 V, 6.3 A
WSI 6/LD 60-150V LLC
150 V, 6.3 A
WTR 2.5 STB
500 V, 24 A
WTR 2.5
500 V, 24 A
WTR 4 STB
400 V, 32 A
WTR 4
400 V, 32 A
WMF 2.5 DI
500 V, 20 A
WMF 2.5 DI PE
500 V, 20 A
WMF 2.5 DI PE STB
500 V, 20 A
WTR 4/SI LD 36V
36 V, 6.3 A
WTR 4/SI LD 150V
150 V, 6.3 A
WTR 4/SI LD 70V
70 V, 6.3 A
WTR 4/SI LD 250V
250 V, 6.3 A
WTR 4 SI
250 V, 6.3 A
WMF 2.5
500 V, 24 A
Installation instructions:
See Schedule of Limitations.
Routine tests:
No routine tests are necessary.
[16]
Descriptive Documents
The scheduled drawings are listed in the report no. provided under item no. [ 8 ] on page 1 of this Type Examination Certificate.
[17]
Schedule of Limitations:
These terminal blocks are to be installed within an ATEX certified enclosure with a minimum rating of IP54, suitable for the
intended application.
The enclosure shall bear the following warning dependent on the terminal block model:
“WARNING DO NOT REMOVE OR REPLACE THE FUSE/TEST DISCONNECT SWITCH/FUSE PLUG WHEN ENERGIZED!”
The maximum permitted service temperature of the terminal blocks is 120°C.
[18] Essential Health and Safety Requirements
The Essential Health and Safety Requirements (EHSRs) are covered by the standards listed at item 9.
Additional information
The Registered Trademark, , for Weidmueller Interface GMBH & Co KG may be used as
the company identifier on the marking label.