User Documentation
2222
5. Electrical connection
Warning! Please observe that applications with high insulation voltages
require sufficient space or insulation to adjoining devices, as
well as protection against accidental contact. Generally spea-
king, fer rules with plastic collars are to be used.
5.1 Technical Data
Supply voltage 18 ... 30 Vdc / approx. 1 W
Operating temperature 0 °C ... + 55 °C, VMR 1ph
0 °C ... + 50 °C, VMR 3ph
WAS5 VMR 1ph
Terminal
1 + reset (18 Vdc...30 Vdc)
2 nc
3 – reset
4 nc
5 Input (24Vac/dc...260Vac/dc)
6 Input (24Vac/dc...260Vac/dc)
7 nc
8 nc
9 nc
10 Relay contact 11
11 Relay contact 12
12 Relay contact 14
Connection cross-section max. 2.5 mm
2
Multi-wire connection max. 1 mm
2
(two wires with the same cross-section)
WAS2 VMR 3ph
Terminal
1 1 input L1 (200Vac/dc…400 Vac/dc)
2 nc
3 Input L1 (80Vac/dc…250 Vac/dc)
4 Input L2 (80Vac/dc…250 Vac/dc)
5 Input N
6 Input L3 (80Vac/dc…250 Vac/dc)
7 Upper limit value relay contact 11
8 Upper limit value relay contact 12
9 Upper limit value relay contact 14
10 Lower limit value relay contact 21
11 Lower limit value relay contact 22
12 Lower limit value relay contact 24