User Documentation
14
3.3 Modules with relay output
SW3=OFF: hysteresis approx. 5% of the set value
SW3=ON: hysteresis app. 10% of the set value
SW4=OFF: relay switches when input > threshold value
SW4=ON: relay switches when input < threshold value
Signal Range SW1 SW2 SW3 SW4
Input 1 Aac OFF ON
5 Aac ON OFF
10 Aac OFF OFF
Signal Range SW1 SW2 SW3 SW4
Input 20 Aac OFF OFF
40 Aac ON OFF
60 Aac ON ON
3.4 Modules with analog outputs
Signal Range SW1 SW2 SW3 SW4 SW5
Input 5/20/40 Auc OFF OFF
10/25/50 Auc OFF ON
30/60 Auc ON OFF
AC Current ON
DC Current OFF
Output 0...10 V ON OFF
0...20 mA OFF OFF
4...20 mA OFF ON