User Documentation
7  Commissioning
WARNING!
Manipulation of the control unit!
During commissioning, the system may be 
manipulated to such an extent that can result 
in risks to life and material damage.
 ▶ Make sure that system components can-
not start up unintentionally!
The procedures applied during commissioning depend on 
which control unit is being used on site. The descriptions in 
this chapter use commissioning with the Siemens SIMATIC 
Manager Step7 (from V5.5 SP2 on) as an example. 
7.1  Requirements
Before you start the commissioning work, the following re-
quirements must be fullled.
 – The control unit must be in operation.
 – The UR67 modules must be completely assembled and 
wired up.
 – The control unit and the UR67 modules must be con-
nected via fieldbus, and a PC/laptop must also be con-
nected.
 – The power supply must be turned on.
7.2  Device description les
Downloading and installing les
 ▶ Download the device description files from the 
Weidmüller website.
Module GSD file
Plastic housing, 30mm wide (A):
UR67-PB-12-8DI-8-30K, UR67-PB-12-8DIO-8-30K
WIUR09C9.GSD
Plastic housing, 60mm wide (B): 
UR67-PB-78-16DI-12-60K, UR67-PB-78-16DIO-12-60K
WIUR09CA.GSD
Metal housing (zinc diecast) completely potted, 
60mm wide (C)
: (UR67-PB-78-8DIDO-12-60M), 
UR67-PB-78-16DI-12-60M, UR67-PB-78-16DO-12-60M
WIUR0E94.GSD
 ▶ If bitmap files for visualising the modules 
are also supplied, store them in the same 
folder as the device description files.
Projects must not be open in the hardware 
conguration tool while the les are being 
installed!
 ▶ Close any open projects before installing 
the device description files!
 ▶ In the hardware configuration tool, open: Extras/Install 
GSD files.
 ▶ Select the directory in which you have stored the device 
description files.
The les available are displayed.
Selecting GSD file
 ▶ Select the files that you would like to install.
 ▶ Click Install.
 ▶ When the installation is complete, click Close.
 ▶ Update the device catalogue via Extras/Update cata-
logue.
The devices associated with the current device description 
le are now listed in the device catalogue.
Updating device description les
The naming convention for GSD les always follows this pat-
tern: GSDML_V2.31-WI-UR67-20160323.xml. By reading 
off the version (V2.31) and the date (2016/03/23), you can 
nd out the status of a GSD le and determine whether you 
are already using the latest version.
 ▶ Download the latest GSD files from the Weidmüller web-
site.
7 Commissioning | Requirements
372484950000/00/03.2016 Manual UR67-PROIFBUS