User Documentation
9 LED indicators and troubleshooting  
442484950000/00/03.2016 Manual UR67-PROIFBUS
Module LED Status Recommended action
2426390000, 2426380000, 2426400000
BF Red: Fieldbus error, no communication 
Off: No error
 – Red: Check the eldbus cable and the PLC conguration, 
check whether the GSD file is up-to-date
DIA Red: Collection error for peripheral errors 
Off: No error message present
 – Red: Check, on which channel the connected device 
causes an error. At least one channel LED must also 
shine.
US Green: Sensor-/system supply OK
Red: Sensor-/system supply < 18V or > 30V 
Off: No sensor-/system supply 
 – Red: Check the power supply of the module
UL Green: Actuator supply OK
Red: Actuator supply < 18V or > 30V
Off: No actuator supply
 – Red: Check the power supply of the module
ACT Yellow: Data exchange with PROFIBUS master 
Off: No connection
 – Off: Check the fieldbus connection
1 … 8 A 
Status Channel
Yellow: Channel A "On" 
Red: Peripheral error (actuator low voltage, sensor or 
actuator short circuit) 
Off: Not connected, status „Off“, no error
 – Red: Check the connected periphery for short circuit, 
check the power supply of the peripheral device
1 … 8 B 
Status Channel
Yellow: Channel B „On“ 
Red: Peripheral error (actuator low voltage, sensor or 
actuator short circuit) 
Off: Not connected, status „Off“, no error
 – Red: Check the connected periphery for short circuit, 
check the power supply of the peripheral device