User Documentation
7 Example applications | Dual-channel safety door monitoring with automatic reset and controlled shutdown and emergency stop
87u-remote IP20 modules for functional safety manual 1484600000/07/11.2020
Achievable safety rating Category 4 ENISO13849-1
PLe ENISO13849-1
SIL 3 EN62061/61508
Stop category 1 EN60204-1
Features  – Dual-channel monitoring
 – Cross-connection detection
 – Automatic reset
 – Monitoring of external contactors 
(EDM)
Safety sensor / operating 
mechanism
 – Emergency stop button
 – Position switch
 – Optional: brake
Notes  – Autostart is also possible if the NC 
circuits from K3 and K4 are connected 
to 3.3 and 3.4.
 – As soon as the enabling on the 
frequency converter is withdrawn, the 
converter must execute a controlled 
shutdown.
 – Exclusion of fault: No external energy 
might be fed into the control line of 
the brake (e.g. caused by cable fault)
 All examples shown are proposals without 
warranty. In any case the operator has to per-
form a safety review of the entire site.
1.1
1.2
1.3
1.4
3.1
3.2
3.3
3.4
4.1
4.2
4.3
4.4
1.1
1.2
1.3
1.4
2.1
2.2
2.3
2.4
2.1
2.2
2.3
2.4
3.1
3.2
3.3
3.4
4.1
4.2
4.3
4.4
M
UR20-PF-O-2DI-SIL-DLY UR20-4DO-P
K4
K3
K4K3
S1
S3
S2
L+(+24V)
M (0V)
Reset
K4
K3
Emergency stop
Safety door
(closed)
Enable
Converter
Example application for dual-channel safety door monitoring with automatic reset and controlled 
shutdown and emergency stop
1)
 Switchable modules see section4.3
When the emergency stop button is pushed, the 
PF-O-xDI-SIL switches off the 24V supply for the mod-
ules
1) 
within the safety segment and thus also contactors K3 
and K4. The failure of a switching element in the emergency 
stop button or the safety door contact as well as a cross-cir-
cuit in their supply lines does not result in the failure of the 
emergency stop mechanism and is detected within the 
fault-reaction time.
After opening the safety door and the expiration of the delay 
time set in the UR20-PF-O-2DI-SIL-DELAY, the spring-oper-
ated interlock can be activated with the unlock button and 
the safety door can be opened. When the power supply is 
turned off, the safety door cannot be opened if the locking 
mechanism is engaged. We recommend using switches with 
mechanical unlocking capabilities.
The PF-O-xDI-SIL module switches the 24V power 
supply for the following modules
1)
 within the safety segment 
if
 – the emergency stop button is unlocked
 – and the safety door is closed
 – and the feedback circuit (NC contacts of K3 and K4) is 
closed. 
Contactors K3 and K4 are controlled by the PLC and can 
switch on as soon as the PF-O-xDI-SIL has switched 
on the 24V supply. To reset the system, press the reset but-
ton for 0.1 to 2s after switching on the power supply, even 
when automatic reset is used.
7.13  Dual-channel safety door monitoring with automatic reset and controlled shutdown and emer-
gency stop