7 Example applications | Dual-channel safety door monitoring, spring-operated interlock with manual reset and emergencystop
83u-remote IP20 modules for functional safety manual 1484600000/07/11.2020
7.9  Dual-channel safety door monitoring, spring-operated interlock with manual reset and emergen-
cystop
Achievable safety rating Category 3 ENISO13849-1
PLe ENISO13849-1
SIL 3 EN62061/61508
Stop category 0 EN60204-1
Features  – Dual-channel monitoring
 – Cross-connection detection
 – Manual reset
 – Monitoring of external contactors 
(EDM)
Safety sensor/operating 
mechanism
 – Emergency stop button
 – Position switch with interlock
 – Zero-speed monitor
 – Manual unlocking
Notes Exclusion of the fault “Interruption or 
releasing of the activator, error in the 
safety interlock”
 All examples shown are proposals without 
warranty. In any case the operator has to per-
form a safety review of the entire site.
1.1
1.2
1.3
1.4
3.1
3.2
3.3
3.4
4.1
4.2
4.3
4.4
1.1
1.2
1.3
1.4
2.1
2.2
2.3
2.4
3.1
3.2
3.3
3.4
4.1
4.2
4.3
4.4
M
UR20-PF-O-xDI-SIL UR20-4DO-P
K4
K3
K4K3Reset
S1
S2S4
S5 S3
L+(+24 V)
M (0 V)
K4
K3
Emergency stop
Safety door
(closed)
Zero-speed monitoring
Unlocking mechanism
Example application for dual-channel emergency stop monitoring
1)
 Switchable modules see section4.3
When the emergency stop button is pushed, the 
PF-O-xDI-SIL switches off the 24V supply for the mod-
ules
1) 
within the safety segment and thus also contactors K3 
and K4. The failure of a switching element in the emergency 
stop button or the safety door contact as well as a cross-cir-
cuit in their supply lines does not result in the failure of the 
emergency stop mechanism and is detected within the 
fault-reaction time.
A stop is performed by switching off K3 and K4 via the 
PLC. After the motor comes to a stop, as observed by the 
zero-speed monitor, the spring-operated interlock can be 
activated via the unlocking button and the safety door 
can be opened. When the power supply is turned off, the 
safety door cannot be opened if the locking mechanism is 
engaged. We recommend using switches with mechanical 
unlocking capabilities.
The PF-O-xDI-SIL switches on the 24V supply for the 
following modules
1)
 within the safety segment if:
 – the emergency stop button is unlocked
 – and the safety door is closed
 – and the locking mechanism is engaged
 – and the feedback circuit (NC contacts of K3 and K4) is 
closed
 – and the start push button has been pushed and released 
again.
Contactors K3 and K4 are controlled by the PLC and can 
switch on as soon as the PF-O-xDI-SIL has switched on 
the 24V supply.