User Documentation
7 Example applications | Dual-channel safety door monitoring with magnetic switch, automatic reset and emergency stop
82 1484600000/07/11.2020u-remote IP20 modules for functional safety manual 
Achievable safety rating Category 4 ENISO13849-1
PLe ENISO13849-1
SIL 3 EN62061/61508
Stop category 0 EN60204-1
Features  – Dual-channel monitoring PDF-M (as 
per EN 60947-5-3)
 – Cross-connection detection
 – Automatic restart
 – Monitoring of external contactors 
(EDM)
Safety sensor/operating 
mechanism
 – Emergency stop button
 – Magnetic switch with coded magnet
Notes The application must be compatible with 
the automatic start-up function.
 All examples shown are proposals without 
warranty. In any case the operator has to per-
form a safety review of the entire site.
1.1
1.2
1.3
1.4
3.1
3.2
3.3
3.4
4.1
4.2
4.3
4.4
1.1
1.2
1.3
1.4
2.1
2.2
2.3
2.4
3.1
3.2
3.3
3.4
4.1
4.2
4.3
4.4
UR20-PF-O-xDI-SIL UR20-4DO-P
K4
K3
S1 S3
K3 K4
Reset
L+(+24V)
M (0V)
M
K4
K3
Safety door
(closed)
Emergency stop
Example application for dual-channel safety door monitoring with magnetic switch, automatic reset 
and emergency stop
1)
 Switchable modules see section4.3
When the emergency stop button is pushed or the safety 
door is opened, the PF-O-xDI-SIL switches off the 
24V supply for the modules
1) 
within the safety segment and 
thus also contactors K3 and K4. The failure of a switching 
element in the emergency stop button or the safety door as 
well as a cross-circuit in their supply lines does not result in 
the failure of the emergency stop mechanism and is detect-
ed within the fault-reaction time.
The PF-O-xDI-SIL switches on the 24V supply for the 
modules
1)
 within the safety segment if:
 – the emergency stop button is unlocked
 – and the safety door is closed
 – and the feedback circuit (NC contacts of K3 and K4) is 
closed. 
Contactors K3 and K4 are controlled by the PLC and can 
switch on as soon as the PF-O-xDI-SIL has switched 
on the 24V supply. To reset the system, press the reset but-
ton for 0.1 to 2s after switching on the power supply, even 
when automatic reset is used.
7.8  Dual-channel safety door monitoring with magnetic switch, automatic reset and emergency stop