User Documentation
7 Example applications | Dual-channel safety door monitoring with automatic reset and emergency stop
79u-remote IP20 modules for functional safety manual 1484600000/07/11.2020
Achievable safety rating Category 4 ENISO13849-1
PLe ENISO13849-1
SIL 3 EN62061/61508
Stop category 0 EN60204-1
Features  – Dual-channel monitoring
 – Cross-connection detection
 – Automatic reset
 – Monitoring of external contactors 
(EDM)
Safety sensor / operating 
mechanism
 – Emergency stop button
 – Position switch
Notes The application must be compatible with 
the automatic start-up function.
 All examples shown are proposals without 
warranty. In any case the operator has to per-
form a safety review of the entire site.
1.1
1.2
1.3
1.4
3.1
3.2
3.3
3.4
4.1
4.2
4.3
4.4
1.1
1.2
1.3
1.4
2.1
2.2
2.3
2.4
3.1
3.2
3.3
3.4
4.1
4.2
4.3
4.4
UR20-PF-O-xDI-SIL UR20-4DO-P
K4
K3
K4K3
S1
S3
S2
L+(+24V)
M (0V)
Reset
M
K4
K3
Emergency stopSafety door (closed)
Example application for dual-channel safety door monitoring with automatic reset and emergency 
stop
1)
 Switchable modules see section4.3
When the emergency stop button is pushed or the safety 
door is opened, the UR20-PF-O-2DI-DELAY-SIL switches off 
the 24V supply for the modules
1)
 within the safety segment 
and thus also contactors K3 and K4. The failure of a switch-
ing element in the emergency stop button or the safety door 
contacts as well as a cross-circuit in their supply lines does 
not result in the failure of the emergency stop mechanism 
and is detected within the fault-reaction time.
The UR20-PF-O-2DI-DELAY-SIL switches on the 24V supply 
for the following modules
1) 
within the safety segment if:
 – the emergency stop button is unlocked
 – and the safety door is closed
 – and the feedback circuit (NC contacts of K3 and K4) is 
closed. 
Contactors K3 and K4 are controlled by the PLC and can 
switch on as soon as the UR20-PF-O-2DI-DELAY-SIL module 
has switched on the 24V supply. To reset the system, press 
the reset button for 0.1 to 2s after switching on the power 
supply, even when automatic reset is used.
7.5  Dual-channel safety door monitoring with automatic reset and emergency stop