User Documentation
7 Example applications | Dual-channel light curtain monitoring (AOPD type 4) and emergency stop monitoring
77u-remote IP20 modules for functional safety manual 1484600000/07/11.2020
Achievable safety rating Category 4 ENISO13849-1
PLe ENISO13849-1
SIL 3 EN62061/61508
Stop category 0 EN60204-1
Features  – Dual-channel monitoring
 – Cross-connection detection
 – Start button
 – Monitoring of external contactors 
(EDM)
 – Self-test of the OSSD in the AOPD
Safety sensor/operating 
mechanism
 – Emergency stop button
 – AOPD type 4 (2 semiconductor 
outputs, P-switching)
Notes Autostart is possible if the NC circuits 
from K3 and K4 are attached to 3.3 and 
3.4.
 All examples shown are proposals without 
warranty. In any case the operator has to per-
form a safety review of the entire site.
1.1
1.2
1.3
1.4
3.1
3.2
3.3
3.4
4.1
4.2
4.3
4.4
1.1
1.2
1.3
1.4
2.1
2.2
2.3
2.4
2.1
2.2
2.3
2.4
3.1
3.2
3.3
3.4
4.1
4.2
4.3
4.4
M
UR20-PF-O-DELAY-SIL
LC1
S1
UR20-4DO-P
L+(+24 V)
K4
K4
K3
K3
Restart
K4
K3
M(0 V)
+ OSSD1OSSD2
–
AOPD type 4 (receiver)
Emergency stop
Example application for dual-channel light curtain monitoring (AOPD type 4) and emergency stop 
monitoring
1)
 Switchable modules see section4.3
When the emergency stop button is pushed or the ac-
tive optoelectronic protective device (AOPD) reacts, the 
UR20-PF-O-2DI-DELAY-SIL switches off the 24V supply for 
the modules
1) 
within the safety segment and thus also for 
contactors K3 and K4. The failure of a switching element 
in the emergency stop button or the AOPD as well as a 
cross-circuit in their supply lines does not result in the failure 
of the corresponding safety device and is detected within 
the fault-reaction time. For this purpose, the AOPD must 
generate a test pulse on its safety outputs at least once per 
second.
When using a UR20-PF-O-2DI-DELAY-SIL: If the DIP switch 
which is assigned to the corresponding safety circuit is 
switched on (in the example DIP switch 2 for LC1) so that 
an AOPD generating own test pulses can be connected, it 
might be necessary to have a shielded cable installation and 
cross-circuit fault detection via the AOPD, depending on the 
required safety level.
The UR20-PF-O-2DI-DELAY-SIL switches on the 24V supply 
for the modules
1)
 within the safety segment if:
 – the emergency stop button is unlocked
 – and the active optoelectronic protective device (AOPD) is 
free
 – and the feedback circuit (NC contacts of K3 and K4) is 
closed
 – and the start push button has been pushed and released 
again.
Contactors K3 and K4 are controlled by the PLC and can 
switch on as soon as the UR20-PF-O-2DI-DELAY-SIL has 
switched on the 24V supply.
7.3  Dual-channel light curtain monitoring (AOPD type 4) and emergency stop monitoring