User Documentation
6 Installation and replacement 
71u-remote IP20 modules for functional safety manual 1484600000/07/11.2020
WARNING
Explosion risk!
 ▶ Before assembly or replacement, make 
sure that there is not a potentially explo-
sive atmosphere!
 ▶ For applications in potentially explosive 
atmospheres, observe the installation and 
construction requirements of EN60079-
15 and/or country-specific regulations.
WARNING
Dangerous contact voltage!
 ▶ All work on the u-remote station must be 
carried out with the power supply discon-
nected. 
 ▶ Make sure that the place of installation 
(switch cabinet etc.) has been 
disconnected from the power supply!
ATTENTION
The product can be destroyed by elec-
trostatic discharge!
The components in the u-remote series can 
be destroyed by electrostatic discharge.
 ▶ Please make sure that personnel and work 
equipment are sufficiently earthed!
 ▶ Carry out all work during the installation and removal as 
well as replacement of components as described in the 
u-remote manual.
When using modules for functional safety (safe I/O modules 
or safe power-feed modules), please observe the following 
additional notes:
 – The modules may only be installed in lockable switch 
cabinets which meet protection class IP54.
 – Please use wire-end ferrules in combination with flexible/
multi-conductor cables. 
 – Ensure that external short circuits due to the cabling can-
not occur for safety inputs in the configuration without 
test pulses (see DINENISO13849-2 Table D.4).
Once an electronic unit is removed from a safe 
power-feed module, the inputs and outputs of the 
subsequent modules are no longer supplied with 
power. This is equivalent to triggering the con-
nected safety equipment!
6  Installation and replacement