User Documentation
5 Detailed descriptions of safe modules | Safe power-feed module UR20-PF-O-2DI-DELAY-SIL
66 1484600000/07/11.2020u-remote IP20 modules for functional safety manual
4321
ON DIP
4321
ON DIP
DIP switch on the UR20-PF-O-2DI-DELAY-SIL
Input Delay Function
1 2 3 4
X X X Safety input0 evaluating own test pulses
X X X Safety input0 no test pulses
X X X Safety input1 evaluating own test pulses
X X X Safety input1 no test pulses
X X 24V Safe: no delay
X X 24V Safe: delay 1 second
X X 24V Safe: delay 30 seconds
X X 24V Safe: delay 60 seconds
Setting options for the DIP switch
= ON
= OFF
X = setting not relevant
ATTENTION
To ensure the safety functions regard the following instruc-
tions for adjustment:
– DIP switches of equal numbers must have identical posi-
tions in both rows.
– If an external device generating pulses is connected to a
safety input of the UR20-PF-O-2DI-DELAY-SIL, this input
must be operated in mode “no test pulses” (DIP switch
setting “ON”).
– When operating in mode “no test pulses”:
– The test pulses of the external device must be shorter
than 2ms, otherwise the safe output will be deacti-
vated.
– A safe laying of cables can be neccessary depending
on the required safety level.
▶ Please use e.g. a ball pen to set the DIP
switches and avoid spiky or sharp-edged tools.