User Documentation
Getting to know and arranging the web server | Setting up the Ethernet socket
11u-remote web server manual2112220000/05/01.2018
3.7 Setting up the Ethernet socket
If you want to use the web server via Ethernet you have to
set up the ethernet connection st.
▶ Connect the PC with the coupler (or a switch within the
network) using a LAN cable.
▶ Click on the coupler in the station view and then on
“Parameter“.
▶ Define the IP address, subnet mask and gateway to be
used.
▶ Make sure, that the parameter “Webserver over Ethernet”
is enabled.
Setting up the ethernet socket
▶ Click on “Apply changes“.
▶ Remove the USB cable between coupler and PC.
▶ Restart the coupler.
Any change of IP settings of USB or Ethernet port will only
be effective after restarting the coupler.
3.8 HTTPS
With HTTPS, the web server and client communicate en-
crypted on the transport layer. This ensures the authenticity
of the server as well as the integrity and condentiality of the
data transmitted.
The following u-remote couplers support HTTPS:
Best.-Nr. Coupler Firmware
version
Hardware version
1334910000 UR20-FBC-EC 00.06.01 02.00.00 or higher
2476450000 UR20-FBC-MOD-TCP-V2 00.03.02 –
1334920000 UR20-FBC-EIP 00.03.02 02.00.00 or higher
1334940000 UR20-FBC-PL 01.03.00 –
The couplers require FSBL version 01.02.00 or
later. You can download the latest FSBL version
from the Weidmüller website.
You can view the FSBL version in the coupler component
view under “General data / Firmware version / FSBL version”.
You can update the FSBL just like the rmware. The FSBL
can be updated independently of the rmware.
These couplers have a u-remote standard certicate. The
certicate is self-signed and valid until 2038. The certicate
cannot be deleted and is always active if no user-dened cer-
ticate is used.
The “HTTPS setting” coupler parameter determines whether
the web server can be addressed via HTTPS and HTTP or
only via HTTPS.
“HTTPS setting” parameter