9.2  Forcing via the station view
 ▶ Click on the channel to be forced.
Dependent on the module type there are different options:
 ▶ To switch an output, click the switch and then Force.
Forcing an output 
 ▶ To force counter readings, type in the force values and 
click Force.
Forcing of modules with registers
 ▶ To force status or control registers (e.g. with counter mod-
ules or PWM modules), click on the corresponding entry.
Forcing registers
 ▶ Set or remove the check mark for each register to be 
forced and click Apply changes.
 ▶ Click Force.
The changes are transferred to the coupler.
9.3  Forcing via the detail view
For a better survey change to the detail view. In this view 
modules can be shown and hidden, which is helpful, espe-
cially when working with larger stations.
 ▶ Click Force/Station.
Switching to detail view in force mode 