8  Congurationandstationdata
8.1  Saving or loading station parameters
Via the stations parameters function, you can save the current 
conguration of the u-remote station or load an existing con-
guration into the coupler. This makes arranging several sta-
tions of identical setup very easy. 
A saved conguration can only be loaded into 
the coupler, if the u-remote stations are physically 
identical (number, sequence and type of modules 
that are registered by the web server, see sec-
tion5.1)
The following information will not be saved by 
the stations parameters function:
 – IP address
 – Gateway
 – Subnet mask
For Modbus-TCP coupler only: The IP address will 
be set to 0.0.0.0 when loading a conguration 
into the coupler.
 ▶ In the menue bar, click Extras/Stations parameters.
Menue Extras/Stations parameters
Saving or loading stations parameters
 ▶ To save the configuration, click Save.
The parameter.bin le is saved in the folder that is set as stor-
age location for downloads in your browser.
 ▶ To load an existing configuration, click Load. 
 ▶ Navigate to the desired configuration file and click Open.
When using PROFINET or PROFIBUS you can con-
tinue working.
 ▶ With all other fieldbus protocols you have to 
restart the coupler.
8.2  Renaming channels
Via the tag names function, you can dene individual names 
for the channels of each module. The tag names of the entire 
station are saved in a csv le. You can transfer this le to oth-
er stations of identical structure to use the same tag names 
on all stations. The user-dened tag names can be deleted 
and reset to default at any time.
 ▶ In the menue bar, click Extras/Tag names.
Menue Extras/Tag names
Creating tag names