User Documentation
7 Example applications | Dual-channel safety door monitoring with proximity sensors, automatic reset and emergency stop
85u-remote IP20 modules for functional safety manual 1484600000/07/11.2020
7.11  Dual-channel safety door monitoring with proximity sensors, automatic reset and emergency 
stop
Achievable safety rating Category 3 ENISO13849-1
PLd ENISO13849-1
SIL 2 EN62061/61508
Stop category 0 EN60204-1
Features  – Dual-channel monitoring
 – Cross-connection detection
 – Automatic reset
 – Monitoring of external contactors 
(EDM)
Safety sensor/operating 
mechanism
 – Emergency stop button
 – 2 proximity switches
Notes  – The power supply for the proximity 
switches is not shown!
 – The application must be compatible 
with the automatic start-up function.
 All examples shown are proposals without 
warranty. In any case the operator has to per-
form a safety review of the entire site.
1.1
1.2
1.3
1.4
3.1
3.2
3.3
3.4
4.1
4.2
4.3
4.4
1.1
1.2
1.3
1.4
2.1
2.2
2.3
2.4
3.1
3.2
3.3
3.4
4.1
4.2
4.3
4.4
M
UR20-PF-O-xDI-SIL UR20-4DO-P
K4
K3
K4K3
Reset
S1
S2
S3
L+(+24 V)
M (0 V)
K4
K3
Emergency stop
Example application for dual-channel safety door monitoring with proximity detectors, automatic 
reset and emergency stop
1)
 Switchable modules see section4.3
If the emergency stop button is pushed or at least one mag-
netic switch is opened, the UR20-PF-O-xDI-SIL switches off 
the 24V supply for the modules
1)
 within safety segment and 
thus also contactors K3 and K4. The failure of a switching 
element in the emergency stop button or a cross-circuit in its 
supply lines does not result in the failure of the emergency 
stop mechanism and is detected within the fault-reaction 
time.
The UR20-PF-O-xDI-SIL switches on the 24V supply for 
modules
1)
 within the safety segment if 
 – the emergency stop button is unlocked
 – and both magnetic contacts are closed
 – and the feedback circuit (NC contacts of K3 and K4) is 
closed. 
Contactors K3 and K4 are controlled by the PLC and can 
switch on as soon as the UR20-PF-O-xDI-SIL has switched 
on the 24V supply. To reset the system, press the reset but-
ton for 0.1 to 2s after switching on the power supply, even 
when automatic reset is used.