5 Detailed descriptions of safe modules | Safe power-feed module UR20-PF-O-2DI-DELAY-SIL
66 1484600000/07/11.2020u-remote IP20 modules for functional safety manual 
4321
ON DIP
4321
ON DIP
DIP switch on the UR20-PF-O-2DI-DELAY-SIL
Input Delay Function
1 2 3 4
X X X Safety input0 evaluating own test pulses
X X X Safety input0 no test pulses
X X X Safety input1 evaluating own test pulses 
X X X Safety input1 no test pulses
X X 24V Safe: no delay
X X 24V Safe: delay 1 second
X X 24V Safe: delay 30 seconds
X X 24V Safe: delay 60 seconds
Setting options for the DIP switch
  = ON
  = OFF
 X  = setting not relevant
ATTENTION
To ensure the safety functions regard the following instruc-
tions for adjustment:
 – DIP switches of equal numbers must have identical posi-
tions in both rows.
 – If an external device generating pulses is connected to a 
safety input of the UR20-PF-O-2DI-DELAY-SIL, this input 
must be operated in mode “no test pulses” (DIP switch 
setting “ON”).
 – When operating in mode “no test pulses”:
 – The test pulses of the external device must be shorter 
than 2ms, otherwise the safe output will be deacti-
vated.
 – A safe laying of cables can be neccessary depending 
on the required safety level.
 ▶ Please use e.g. a ball pen to set the DIP 
switches and avoid spiky or sharp-edged tools.