User Documentation
8 LED displays and troubleshooting | Safe I/O modules
90 1484600000/07/11.2020u-remote IP20 modules for functional safety manual 
UR20-8DI-PN-FSOE, UR20-8DI-PN-FSOE-V2, UR20-8DI-PN-FSPS, UR20-8DI-PN-FSPS-V2
LED Status Recommended action
Status LED Red:
 – Module has not been snapped properly
 – Error in the supply voltage
 – Check that the module has been snapped into place properly 
 – Check supply voltage
 – Internal error detected  – Module might have switched off caused by overtemperature; check the 
temperature inside the switch cabinet
If the error has not been xed, send the module to Weidmüller for a technical 
examination.
 – Safety address is not set properly  – Check the safety address (e.g. via the web server)
 – If no address is displayed in the web server set the safety address again 
as described in section 3.5
 – Communication failure  – Check wiring
 – Restart the coupler
Flashes alternating red and green.
 – 3s green / 1s red: Module is waiting for parameters from the safety 
control (e.g. after the power up) or safety address is not set according 
to the project plan
 – 1s green / 1s red: Error pending
 – Intervention via the safety control is needed
1.1 / 1.4
2.1 / 2.4
3.1 / 3.4
4.1 / 4.4
Yellow: Input 0 / 1 active 
Yellow: Input 2 / 3 active 
Yellow: Input 4 / 5 active 
Yellow: Input 6 / 7 active
1.3 
2.3
3.3 
4.3
Red: Error input 0 / 1 
Red: Error input 2 / 3 
Red: Error input 4 / 5 
Red: Error input 6 / 7
 – At least one AUX-O is overloaded or short circuit with the supply voltage
 – Readback error on the test pulses of at least one input (e.g. caused by 
external short circuit)
 – The parameterised discrepancy time of this pair of inouts has been 
exceeded
 – Check wiring
 – Check parameterisation
If the error has not been xed, send the module to Weidmüller for a technical 
examination.










