Setting PROFIsafe on Siemens PLC with TIA Portal 
xxxxxx0000/01/05.2016    19 
PROFIsafe parameter settings 
1) Set the Source F-Address (F-CPU)  
2) Set the F-Address of the module with the DIP switches 
NOTE: Each address change needs first an address set to “0” and power up the 
module. Then set the new address and power up the module again.  
3) Set the Destination F-Address (I/O Device or DP-Slave e.g UR20)according to the 
DIP switches of the module
4) Set the check sum CRC getting from the CPD Tool (see the next page) 