Product Change Notification
Copyright © 2014-2017 Weidmüller Interface GmbH & Co. KG            1 / 5   
All rights reserved. Reproduction without permission is prohibited. 
Firmware change-log of new features and bug fixes of the u-remote modules:  
Firmware updating Information: 
An update of the firmware can be done via the embedded web server. A description of the firmware update can be 
found in the u-remote web server manual on the Weidmüller website: www.weidmueller.com 
UR20-1COM-232-485-422 (1315750000)  
Version 01.00.16              Release date: July, 2019 
• Increased size of RX buffer to 4kByte 
• Fixed that the module could freeze when the force modus is used or after a software reset of the fieldbus  
 coupler 
Version 01.00.14             Release date: October 04, 2018 
• Fixed that RX Hardware buffer can be flushed now after a buffer overflow 
Version 01.00.13               Release date: July 2018 
• Fixed that the status bit IX0.7 is set to “1” while the module is deactivated 
• Bit for Function "DisableSend_TX_HWBUFFER" now working correctly 
Version 01.00.12              Release date: December 2017 
• Fixed that an acknowledge response in rare cases could be transmitted before all data was received 
• Fixed that sometimes a received data overflow was not handled correctly 
• Added CRC16 checksum calculation for incoming and outgoing data 
Version 01.00.11               Release date: June 06, 2016 
• First released version 
UR20-1COM-SAI-PRO (2007430000) 
Version 01.02.00 Release date: September 2020 
• New feature: Option handling is supported without power cycle of the UR20-1COM-SAI-PRO module 
•  Bug fix: Improved start up behaviour for SAI-AU SB 8DIO and SAI-AU SB 8DI modules 
Version 01.01.00              Release date: March 2018 
• Fixed behaviour of status LED after power cycle or low voltage for all hardware versions 
Version 01.00.07              Release date: December 2017 
• Minor improvements 
Version 01.00.06               Release date: May 17, 2017 
• New feature: Improved overcurrent detection for sub bus supply (works with HW-Version >01.05.00) 
• Bug Fixes: parameter for substitute values is working now 
Version 01.00.04              Release date: October 04, 2016 
Bug Fixes: Improved start up behaviour while initialising sub bus modules. 
    A firmware update is recommended! 
Version 01.00.01               Release date: June 06, 2016 
• First released version 
UR20-2AI-SG-24-DIAG (1990070000) 
Version 01.01.00 Release date: September, 2020 
•  New feature: Extended value range for sensor sensitivity 
Version 01.00.06                Release date: April, 2018 
• Known issue: Calibration sheet cannot be downloaded when coupler firmware with release date July 2019 
  is used 
• Offset can be changed independently for each entered value of the sensor sensitivity. A description 
  of changes in the calibration process can be found in the UR20 manual (v13 or above). 
Version 01.00.04               Release date: December 2017 
• Improved algorithm for calculation of user offset in combination with manual tare 
• Added blocking of tare function when input data is out of range 
• Version is removed from download section – upgrade to newest version is recommended! 
Version 01.00.03              Release date: October 04, 2016 
• First released version 
UR20-3EM-230V-AC (2007420000) 
Version 01.00.47              Release date: December 2017 
• Fixed that value of Fundamental Reactive Power sometimes could be inaccurate 
Version 01.00.46                Release date: May 17, 2017 
• New feature: adds Parameter “direction recognition” indicate 3 phase direction 
Version 01.00.30              Release date: October 04, 2016 
• Bug Fixes: Improved diagnosis threshold values for voltage and current: Diagnostic LED threshold behaviour 
adjusted. 
Version 01.00.28               Release date: June 06, 2016 
• First released version 