Product Change Notification

Copyright © 2020 Weidmüller Interface GmbH & Co. KG 2 / 6
All rights reserved. Reproduction without permission is prohibited.
Bug fixes:
Diagnostic data mapping is corrected for module UR20-PF-O-2DI-DELAY-SIL.
Modbus TCP slave (server): solved "failed to allocate mapping" error.
Known issues:
Manually stopping and starting of the PLC application won't start Modbus master (RTU). A redeploy solves the
issue.
Node-RED: 'iodata-out' does not accept set values when variable is of type 'TIME'.
OPC UA: write access to variables of type 'TIME' is currently not possible.
Firefox: 'Private Mode' is currently not supported.
Remove a module after Autoscan operation and the follow up deploy operation fails. A power cycle is
necessary to solve this error.
Version 1.7.0 Hardware Version 01.xx.xx Release date: April, 2020
New features:
Modbus TCP Slave
Global system status information
Node-RED: upgrade to version 1.0.3
Usage of the second Ethernet port (X2) is now supported.
User defined NTP server parameters
Visu: configured widget visibility
Information:
Online help supports search operation.
Bug fixes:
Node-RED: installation of additional nodes might fail with error "EACCES: permission denied".
Known issues:
Node-RED: 'iodata-out' does not accept set values when variable is of type 'TIME'.
OPC UA: write access to variables of type 'TIME' is currently not possible.
Firefox: 'Private Mode' is currently not supported.
Remove a module after Autoscan operation and the follow up deploy operation fails. A power cycle is
necessary to solve this error.
Configuration of UR20-PF-O-2DI-DELAY-SIL module maps diagnostic data in a wrong way.
Version 1.6.0 Hardware Version 01.xx.xx Release date: February, 2020
New features:
Weidmüller products 'Managed Switch' are supported regarding DHCP handling.
Information:
Usage of the second Ethernet port (X2) is not possible yet and will be added in a future firmware update.
Node-RED: flow size is limited to 3 MB per export/import operation.
Bug fixes:
Node-RED: flow size is increased from 1 to 3 MB.
OPC UA: the variable identifier now corresponds to the global variable, hence it will only change if the variable
name changes
Known issues:
Node-RED: installation of additional nodes might fail with error "EACCES: permission denied". A factory reset
solves this issue.
Node-RED: 'iodata-out' does not accept set values when variable is of type 'TIME'.
OPC UA: write access to variables of type 'TIME' are currently not possible.
Firefox: 'Private Mode' is currently not supported.
Remove a module after Autoscan operation and the follow up deploy operation fails. A power cycle is
necessary to solve this error.
Version 1.5.0 Hardware Version 01.xx.xx Release date: January, 2020
New features:
Device Live View Monitoring the device configuration of the real-time application
Network setting supports beside static also dynamic IP configuration (DHCP).
Information: